The following tables shows the available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Settings switching behavior/Regulation
Constant light controlled by
external object
Presence
Adjustment of the switch on
behavior
Switch On control delay
1s
–
5min
[5s]
Adjustment of the delay
between activation and start
of regulation
Use switch on dimming value
Parameter (select
dimming value)
TeachIn (teached dimming
value)
Calculate switch on value
Adjustment of the power up
value
Brightness value [Lux] for
switch on
use last dimming setpoint
use parameter value
Adjustment if the last setpoint
shall be calculated from
relative dimming, the secenes
or being load from the
parameters
Controller switches light off
locked
enabled
Adjustment if the controller
may switch the light off at a
strong sun radiation
Use Day / Night object
not used
use for next switch on
use directly and for next
switch on
Activates the usage oft he
day/night switchover. At
activated day/night
switchover, two setpoints (day
and night) are shown
otherwise only one setpoint is
shown
Setpoint for day
100
–
750 Lux
[450 Lux]
Setpoint for day mode
Setpoint for night
100
–
750 Lux
[100 Lux]
Setpoint for night mode
Settings for the dimming behavior
Cyclical sending of dimming
value
not used
12 s -10 min
defines the time for the cyclic
sending of the dimming value
Send dimming value on
change of
0-20%
[2%]
defines the minimal change
for sending the dimming value
CL behavior at relative
dimming
use new dimming value
Disable CL control
Adjsutment if regulation stays
active at relative dimming
Relative dimming time
5
–
60s
[20 s]
defines the time for dimming
from 0 to 100%
Table 24: Setting options - Constant Light Control / 1