The following table shows the possible settings for this menu:
ETS-Text
Dynamic range
[Default value]
Comment
Day/Night Object
not used
used
used, read after reset
Setting whether a day/night
object is to be used and
whether it should be queried in
the case of a reset.
Value for Day/Night
Day = 0 / Night = 1
Day = 1 / Night = 0
Polarity of the Day/Night object
Toggle Day/Night
At next Presence
directly at toggle
Setting when day/night
changeover is active
Basic setting of sensitivity
Release sensitivity for day
1-8
[6]
Setting of the release sensitivity
in day mode
Release sensitivity for night
1-8
[3]
Setting of the release sensitivity
in night mode
Presence sensitivity
1-8
[8]
Sensitivity adjustment when
presence detected
Basic settings of brightness
Switch-on threshold
–
day
10-2000Lux
[200]
Setting of the brightness
threshold below which the
sensor is activated in day mode
Switch-on threshold
–
night
10-2000Lux
[10]
Setting of the brightness
threshold below which the
sensor is activated in night
mode
Switch-off when exceeding
not active
10-2000Lux
Setting of the brightness
threshold from which the
sensor is deactivated
Forced retrigger
not active
After presence and
follow-up time
after fix time
Activation of a filter for short-
term brightness fluctuations
Follow-up time for force
30s-12h
Setting the release/follow-up
time
Release time for push button
long (Manual => Auto)
After presence and
follow-up time
after fix time
Activation of a release time
from the override by an
external push button
Follow-up time for push
button/
Release time for push
button
30s-12h
Setting the release/follow-up
time
C li al se di g heart eat
not active
1min
–
24h
Activation of a cyclic
"heartbeat" telegram
Table 2: Parameter - General Settings