Technical Manual Presence Detector SCN-P/G360XX.02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 •
Fax: +49-2263-4588
• [email protected] • www.mdt.de
46
46
ETS-Text
Dynamic range
[Default value]
Comment
Settings standby/orientation light
Standby/orientation light
not used
used
Setting whether the light
should continue to run after it
has been switched off
Standby setpoint
100
–
750 Lux
[100 Lux]
Value for Standby setpoint
Standby time
5s
–
60min
[15s]
Lenght of Standby time
Settings lock object
Lock object active
Yes
No
Activates a locking object
Lock object
value = 1
Off
On (100%)
No change (hold value)
Select value
Settings what should happen
when the lock object is
activated
Value set
0-100%
[0%]
Defines value for enabled lock
object.
Only visible if lock object
"Select value" is active
Lock object
value = 0
Off
On (100%)
No change (hold value)
Restore previous state
Settings what should happen
when the lock object is
deactivated
Settings scenes
Scenes
not used
used
Setting whether scenes are to
be used for constant light
control
Scene 1 - 8
100
–
750 Lux
[500 Lux]
Adjustable values for the
different scenes
Table 25: Setting options - Constant Light Control / 2
The parameters are described below:
Settings switching behavior/Regulation
The general settings for constant light control are made here. The "Switch constant light
with" parameter can be used to set whether the control is switched via the detected
presence or via an external object which can be connected, for example, to a push-button.
The "Dimmer switch-on value via" parameter can be used to specify to the presence detector
the value with which the control is to be started. It is possible both to define a fixed value
and to take the value calibrated during the Teach-In procedure or to have the switch-on
value calculated directly internally. The time until the control starts after switching on can