4.7 Calibration of brightness value
The following figure shows the individual cell options for calibrating the brightness value:
Figure 22: Calibration brightness value
The following table shows the possible settings for this parameter:
ETS-Text
Dynamic range
[Default value]
Comment
Correction Lux value
-50% to 70%
[0%]
Increase/decrease by the set
value
Room reflection factor
1
0,7 very high
0,5 high
0,4 medium
0,3 low
0,25 low
0,2 very low
Reflectance of the
environment:
Indicates how much of the
light is reflected back
(1=100%, 0 = 0%)
Lux value for TeachIn
200-1000
[450]
Adjustment value for external
read-in
Use TeachIn at application
download
Hold TeachIn value
Use default value
Defines whether the presence
detector should hold the
teach-in values after the
download or load the factory
settings.
Table 20: Calibration of brightness value
The individual parameters are described in more detail below:
Correction Lux value
With the correction of the lux value, the measured lux value is shifted by an adjustable
percentage offset. Thus, at a set value of -50%, the measured value is reduced by 50%. Thus
the presence detector would output the value 200 at a measured value of 400 lux and a
correction value of -50%.