Model: MC-1-DE
Doc Ref. No:-m05dom102
Issue No:-00
Page 61 of 76
User’s Manual
11. Ethernet Communications: Telnet, SNMP
11.1 Telnet
After network connection established the GPS TIME SYNC UNIT MC-1-DE can be configure remotely
from a work station using command line interface (Telnet). Telnet configuration GPS TIME SYNC
UNIT MC-1-DE is password protected. GPS TIME SYNC UNIT MC-1-DE model several parameters
can configure using Telnet are shown in Table. To setup a Telnet connection please refers Appendix
E1. MC-1-DE supports only one Telnet session at a time. If the system is not disconnected properly
then Telnet session will be timed out and disconnected after 10 minutes.
Command
Description
Reference
H
Command list supported by model MC-1-DE Model
Appendix E1
Appendix E1
CC
To view Current Configuration of model MC-1-DE model.
IP
Sets the network IP address, Ethernet port, of model MC-1-
DE. After this command connection to Telnet prompt will be
lost and user needs to reopen Telnet prompt. Factory set val-
ue is : 192.168.100.153
MASK
Sets the Network IP mask address, Ethernet port, of model
MC-1-DE. Factory set Value is : 255.255.255.0
GTY
Sets the Network IP Gateway (factory set route address),
Ethernet port, of model MC-1-DE.
Factory set Value is : 192.168.100.001
SIP1
Sets the IP address of SNMP manager which should receive
any Trap massages generated by model MC-1-DE Agent.
Factory set value is 192.168.100.226
SIP2
Sets the IP address of SNMP manager which should receive
any Trap massages generated by model MC-1-DE Agent.
Factory set value is 192.168.100.226
SRC
Sets the SNMP Read Community. The input could be any
ASCII string with 1-20 characters. Factory set value is: masi-
bus
SWC
Sets the SNMP Write Community. The input could be any
ASCII string with 1-20 characters. Factory set value is masi-
bus.
STRT
Used to modify stratum of model MC-1-DE when it is not syn-
chronized. Factory set value is 1. For detail about stratum re-
fer Section 9.4.
U
Sets the User name Telnet session, current Ethernet port, of
model MC-1-DE.Factory set Value is masibus (case sensi-
tive).
P
Sets the Password Telnet session, current Ethernet port, of
model MC-1-DE. Factory set Value is masibus (Case Sensi-
tive).
Z
Sets the time zone of MC-1-DE
IRIG
Used to configure UTC/Local time on IRIG output port.
Factory set Value is No – Transmit local time on IRIG-B Port.
I_1344
Used to configure IEEE-1344 C37.118-2005 protocol on IRIG-
B output port. Factory set Value is No-Disable IEEE 1344.
SPD
Set the Propogation Delay needs to apply to receiver.
MT
Sets Manual Time setting.
Q
Quit the telnet configuration
Table 8 Configurable Parameters through Telnet