Model: MC-1-DE
Doc Ref. No:-m05dom102
Issue No:-00
User’s Manual
Page 36 of 76
GPS TIME SYNC UNIT SYSTEM
Version No: 101
UART commands:
SBxx : Set baud rate.
24 : 2400 baud rate.
48 : 4800 baud rate.
96 : 9600 baud rate.
19 : 19200 baud rate.
38 : 38400 baud rate.
57 : 57600 baud rate.
11 : 115200 baud rate.
SPx : Set parity bit.
0 : parity bit set to none.
1 : parity bit set to odd.
2 : parity bit set to even.
SSx : Set stop bit.
1 : stop bit set to 1.
2 : stop bit set to 2.
SUx : Set UTC OR IST time.
1 : UTC time.
2 : LOCAL time.
SPD(xxxxxx) : 1PPS Cable Delay Correction command(Propagation Delay).
: Range: 0 to 99999 ns.
: Default value: 0 ns.
: Resolution: 1 ns.
TC2x : Set transmit mode.
1 : NMEA mode.
2 : t-format mode.
3 : NGTS mode.
P(password) : To change password.
M(time&date) : Manual Time Setting Mode
: Enter command M(hh:mm:ss,dd/mm/yy)
R : Reset the controller.
D : Set to Default Setting.
ETH0 : Set to Default Network Settings.
ETx : To configure additional Events.
EWx : To configure additional Events ON Time.
Z : Set Timezone Setting.
I_1344 : E = Enabled.
: D = Disabled.
IRIG : U = UTC time.
: L = Local time.
ENTER COMMAND TO CONFIGURE PARAMETER
OR PRESS ENTER TO CONTINUE.
---------------------------------------------------
If the user presses the ‘Enter’ key before writing any command, unit will come out of configuration
mode and operator has to enter ‘CONFIG’ and password again. Any pressing of ‘Enter’ instead of
command will result in a jump out of the configuration mode.