Model: MC-1-DE
Doc Ref. No:-m05dom102
Issue No:-00
Page 39 of 76
User’s Manual
Terminal do not match. To correct this, follow the steps 2 and 3 of SBxx command. Now correct the
parameter to match with desired/set ones.
After setting the parity in this setting window, follow the steps 5 and 6 of the SBxx command. The
time data will again re-appear. You can check present settings using ‘L’ command.
8.2.2.3 Command: SSx [Stop Bit Command]
Applicable Options: SS1 / SS2 (Please refer ‘H’ Command menu for applicable meanings of men-
tioned options)
The number of stop bits in the serial communication can be set as 1 or 2 using this command. The
options are simply two:
SS1:
One stop bit
SS2:
Two stop bits
The steps to follow are same as SBxx and SPx command.
8.2.3 Time Zone Offset Command:
Command: Z
This command is to enter the time offset of any particular region/country with reference to the UTC.
Every country local time works at some time offset with respect to UTC. Time offset can be positive or
negative w.r.t. UTC. The table of the time zone offset can be found from Internet.
Time zone offset value should be between time ranges of -12:45 to +12:45.
Time offset value apart from above range will be considered as INVALID command.
The time zone will put its effect on the IRIG-B signal, when the
IRIGB of the unit is configured for Local time as well as it will af-
fect the time on unit, NGTS and T-frame only if the unit is set in
the LOCAL TIME DISPLAY mode, using the SUx command as
explained further.
Example:
Z
ENTER THE TIME-ZONE OFFSET ADDED WITH THE DAY-LIGHT SAVING TIME, IF APPLI-
CABLE.
FORMAT: (+/-)(HH):(MM)
ENTER NOW:
-02:00
COMMAND COMPLETE
ENTER COMMAND TO CONFIGURE PARAMETER.
TO CONTINUE PRESS ENTER