Model: MC-1-DE
Doc Ref. No:-m05dom102
Issue No:-00
Page 65 of 76
User’s Manual
iii) Enter Community/ SNMP version/ Port:
Port: 161
Read Community: masibus (Factory set Value)
Write Community: masibus (Factory set Value)
SNMP Version: 1 or 2 (Select from Dropdown menu)
NOTE: Above value of Read & Write, community is factory set, once they configured SNMP manager
Need to remember to operate or monitor from remote location.
iv) MIB Tree view:
The MIB of the masibus model MC-1-DE includes following parts:
SNMP Object &
OID
Name & OID
Value
Description
Enterprises.38306
masibus
1.3.6.1.4.1.38306
-
Root Node of The masibus MIB
masibus.1
Product_Info
1.3.6.1.4.1.38306.1
String
masibus model MC-1-DE Product
information
masibus.2
GPS_Configuration
1.3.6.1.4.1.38306.2
String
masibus model MC-1-DE SNMP
configuration variable
masibus.3
GPS_Status
1.3.6.1.4.1.38306.3
String
masibus model MC-1-DE Status va-
riables
SNMP Object Product_Info variables
SNMP Branch &
OID
Variable & OID
Data
Type
Description
Product_Info
Name
1.3.6.1.4.1.38306.1.1.0
String (R)
A read Only variable display
Name of Product
Product_Info
Version
1.3.6.1.4.1.38306.1.2.0
String (R)
A read Only variable display
Firmware Version
Product_Info
Date
1.3.6.1.4.1.38306.1.3.0
String (R)
A read Only variable display
Firmware Release Date
SNMP Object GPS_Configuration variables:
SNMP Branch
Variable & OID
Data Type
& Value
Description