Model: MC-1-DE
Doc Ref. No:-m05dom102
Issue No:-00
Page 41 of 76
User’s Manual
ET1 = 60
EW1 = 50
2. If user has to configure event1 at every 60 seconds interval with pulse ON time width of 20% of
event time, below values are to configured for event1 output.
ET1 = 60
EW1 = 12000
3. If user has to configure event1 at every 60 seconds interval with pulse ON time width of 50% of
event time, below values are to configured for event1 output.
ET1 = 60
EW1 = 30000
NOTE:
a) Unit of ETx parameter is seconds and EWx parameter is milliseconds (i.e. 1 sec = 1000 millise-
conds). Please ensure that the instrument should be power switch OFF/ON after changing the
event time settings.
8.2.6 Ethernet Default Command:
Command: ETH0
It is recommended to remove all NTP outputs RJ-45 cable from
network before using this command and stop all the services
such as NTP, SNMP, Telnet with GPS TIME SYNC UNIT MC-1-
DE because this command will set all NTP output ports IP ad-
dress to same IP address as a result of which there will be IP
conflict in network.
This command is used to set default network settings of GPS TIME SYNC UNIT MC-1-DE.
After Applying this command network settings of all NTP output ports will be as below
IP Address
192.168.100.153
Subnet Mask
255.255.255.0
Gateway
192.168.100.1
SNMP Manager1 IP
192.168.100.226
SNMP Manager2 IP
192.168.100.226
Read Community
masibus
Write Community
masibus
Trap Community
masibus
IRIG-B Time
local
IEEE-1344 C37.118-2005 disable
Telnet User Name
masibus
Telnet Password
masibus
Table 2 Ethernet Default command