Level Units
Select the Units of measurement for the level readout:
• Inches
• Feet
• Millimeters
• Centimeters
• Meters
Probe Model
Select the Probe Model to be used with Model 700:
• 7zF Single Rod
• 7zP Coaxial High Pressure
• 7zT Coaxial Standard
• 7z1 Single Flexible Standard
Probe Mount
Select the type of Probe Mounting to the vessel:
• NPT (National Pipe Thread)
• BSP (British Standard Pipe)
• Flange (ASME or EN)
Probe Length
Enter the exact Probe Length as printed on the probe nameplate. Probe Length is
shown as the last three digits of the Probe Model number. Range is 30 cm to 30 meters
(12 inches to 100 feet) probe dependent. Refer to Section 1.4.1.1.
Level Offset
Enter the desired level reading when the liquid is at the end of the probe. Range is -762
cm to 22 meters (-25 feet to 75 feet). Refer to Section 3.4 for further information. (With
default Level Offset = 0, all measurements are referenced from the bottom of the probe.)
Dielectric Range
Enter the Dielectric Range for the material to be measured.
• Below 1.7 (Light hydrocarbons like Propane and Butane)
• 1.7 to 3.0 (Most typical hydrocarbons)
• 3.0 to 10 (Varying dielectric, for example: mixing tanks)
• 10 (Water-based media)
H
A
R
T
O
n
ly
4 mA Set Point
(LRV)
Enter the level value (0 %-point) for the 4 mA point. Lower Range Value (LRV).
Refer to Section 1.4.1.1.
20 mA Set Point
(URV)
Enter the level value (100 %-point) for the 20 mA point. Upper Range Value (URV).
Refer to Section 1.4.1.1.
Failure Alarm
Enter the desired output state when a Failure Indicator is active.
• 22 mA
• 3.6 mA
• Hold (Hold last value is not recommended, unless troubleshooting)