4.0 Advanced Configuration/
Troubleshooting Techniques
This section contains information regarding some of the
advanced configuration and troubleshooting capability con-
tained within the Model 700 transmitter. These diagnostic
options are best suited for use with PACTware and the
Model 700 DTM, and should be implemented only after
contacting MAGNETROL Technical Support.
4.1
End-of-Probe Analysis (EOPA)
Note that due to the operation of this method, End of
Probe Analysis cannot be applied with interface measure-
ment, applications with a "water" bottoms, or with stratify-
ing liquids. Therefore, EOPA will not be available when
Measurement Type = Interface & Level.
When EOPA is enabled and the calculated (inferred level) is
being used, a diagnostic warning shown as "Inferred Level”
will be present.
4.1.1 Enable EOPA using PACT
ware
Click on the Device Setup tab, and then select Advanced
Config. In the lower left corner select the correct Polarity
for the End of Probe pulse, then turn on the EoP Analysis.
The Eop Dielectric box will then appear. Fill in the correct
Dielectric of the process medium being measured.