MHR Radio Controller Instruction Manual
June 2017
Page 52 of 58
Alarm
Number
Alarm
Text
Cause of alarm
Effect of alarm
Recovery Action
38
S38. OUT
7 +VB
SHORT
When the output is
supposed to be at -
VBat, a voltage of 2V
or greater was seen
on the output. The
output was shut off to
prevent damage to
the hardware.
Output is shut off and will
not operate until the cause
is fixed and power to the
system is cycled
Determine the cause of the
short, fix the cause, and power
cycle the system
39
S39. OUT
8 +VB
SHORT
When the output is
supposed to be at -
VBat, a voltage of 2V
or greater was seen
on the output. The
output was shut off to
prevent damage to
the hardware.
Output is shut off and will
not operate until the cause
is fixed and power to the
system is cycled
Determine the cause of the
short, fix the cause, and power
cycle the system
40
S40. OUT
9 +VB
SHORT
When the output is
supposed to be at -
VBat, a voltage of 2V
or greater was seen
on the output. The
output was shut off to
prevent damage to
the hardware.
Output is shut off and will
not operate until the cause
is fixed and power to the
system is cycled
Determine the cause of the
short, fix the cause, and power
cycle the system
41
S41. OUT
10 +VB
SHORT
When the output is
supposed to be at -
VBat, a voltage of 2V
or greater was seen
on the output. The
output was shut off to
prevent damage to
the hardware.
Output is shut off and will
not operate until the cause
is fixed and power to the
system is cycled
Determine the cause of the
short, fix the cause, and power
cycle the system
42
S42. OUT
11 +VB
SHORT
When the output is
supposed to be at -
VBat, a voltage of 2V
or greater was seen
on the output. The
output was shut off to
prevent damage to
the hardware.
Output is shut off and will
not operate until the cause
is fixed and power to the
system is cycled
Determine the cause of the
short, fix the cause, and power
cycle the system
43
S43. OUT
12 +VB
SHORT
When the output is
supposed to be at -
VBat, a voltage of 2V
or greater was seen
on the output. The
output was shut off to
prevent damage to
the hardware.
Output is shut off and will
not operate until the cause
is fixed and power to the
system is cycled
Determine the cause of the
short, fix the cause, and power
cycle the system
Содержание MHR
Страница 1: ...MHR Radio Controller June 2017 Part Number 195 50488 0100 R7 2017 Magnetek Material Handling...
Страница 21: ...MHR Radio Controller Instruction Manual June 2017 Page 20 of 58...
Страница 22: ...MHR Radio Controller Instruction Manual June 2017 Page 21 of 58...
Страница 23: ...MHR Radio Controller Instruction Manual June 2017 Page 22 of 58...
Страница 59: ...MHR Radio Controller Instruction Manual June 2017 Page 58 of 58 8 0 EU DECLARATION OF CONFORMITY...