IMPULSE•G+Mini Advanced Instruction Manual – March 2014
6-6
DNE
Drive Not Ready
User is trying to give a run command while a
FWD or REV is present at Power Up.
1. Check input terminals.
2. Check H01.01 to H01.07 programming.
EF
(flashing)
External Fault
Both FORWARD/UP and REVERSE/DOWN
commands are input at same time for 500 msec
or longer.
1. Check control input wiring.
2. Check the sequence of operation.
EF0
Optional External
Fault
External fault input from communication option
card.
1. Check communication option card
connection and signals.
2. Check external device for any fault(s)
EF1
External
Fault 1
External fault occurs on Terminal S1.
1. Check constant H01.01 for proper
programming.
2. Check the conditions for input terminal S1
(U01.10).
EF2
External
Fault 2
External fault occurs on Terminal S2.
1. Check constant H01.02 for proper
programming.
2. Check the conditions for input terminal S2
(U01.10).
EF3
External
Fault 3
External fault occurs on Terminal S3.
1. Check constant H01.03 for proper
programming.
2. Check the condition for input terminal S3
(U01.10).
EF4
External
Fault 4
External fault occurs on Terminal S4.
1. Check constant H01.04 for proper
programming.
2. Check the condition for input terminal S4
(U01.10).
EF5
External
Fault 5
External fault occurs on Terminal S5.
1. Check constant H01.05 for proper
programming.
2. Check the condition for input terminal S5
(U01.10).
EF6
External
Fault 6
External fault occurs on Terminal S6.
1. Check constant H01.06 for proper
programming.
2. Check the condition for input terminal S6
(U01.10).
EF7
External
Fault 7
External fault occurs on Terminal S7.
1. Check constant H01.07 for proper
programming.
2. Check the condition for input terminal S7
(U01.10).
GF
Ground Fault
Ground Fault.
Current shorted to ground
exceeded 50% of rated current on output side of
the drive. Setting L08.09 to 1 (enable ground
fault detection) in models 2025 and 4014 or
larger.
1. Disconnect motor from drive and check it for
shorts using a megger.
2. Ensure that R/C Surge Suppressors are used
across all brake contactor coils to prevent
disturbance by electrical transients.
HBB
Hardware BB
Hardware Base Block.
The Safe Disable Input
channel is open.
1. Check if external safety circuit tripped and
disabled the drive.
2. If the Safe Disable function is not utilized,
check if the terminals HC and H1 are linked.
LC
Load Check Err
Load Check Alarm.
This fault is displayed
when the load detected is greater than the
measured load during the Load Check set up
process for a particular LC Zone.
1. Reduce Load.
2. Decrease the LC Sensitivity (higher value).
3. Increase the settings for the particular LC
Zone where the fault occurred by 2 or 3.
LC dn
LC Done
Load Check Done Alarm.
This alarm is
displayed after the LC set up process is done.
The alarm will clear when the Down command
is pressed and completes the LC set up process
.
--
Fault Code
Fault or Indicator Name/Description
Corrective Action
Содержание 2001-G+M
Страница 2: ......
Страница 9: ...C h a p t e r 1 Introduction...
Страница 10: ...IMPULSE G Mini Advanced Instruction Manual March 2014 1 2 This page intentionally left blank...
Страница 16: ...IMPULSE G Mini Advanced Instruction Manual March 2014 1 8 This page intentionally left blank...
Страница 17: ...C h a p t e r 2 Installation...
Страница 18: ...IMPULSE G Mini Advanced Instruction Manual March 2014 2 2 This page intentionally left blank...
Страница 25: ...C h a p t e r 3 Wiring...
Страница 26: ...IMPULSE G Mini Advanced Instruction Manual March 2014 3 2 This page intentionally left blank...
Страница 38: ...IMPULSE G Mini Advanced Instruction Manual March 2014 3 14 This page intentionally left blank...
Страница 39: ...C h a p t e r 4 Getting Started...
Страница 40: ...IMPULSE G Mini Advanced Instruction Manual March 2014 4 2 This page intentionally left blank...
Страница 60: ...IMPULSE G Mini Advanced Instruction Manual March 2014 4 22 This page intentionally left blank...
Страница 61: ...C h a p t e r 5 Programming Features...
Страница 62: ...IMPULSE G Mini Advanced Instruction Manual March 2014 5 2 This page intentionally left blank...
Страница 88: ...IMPULSE G Mini Advanced Instruction Manual March 2014 5 28 Figure 5 17 Swift Lift Timing Diagram...
Страница 153: ...Troubleshooting IMPULSE G Mini C h a p t e r 6...
Страница 154: ...IMPULSE G Mini Advanced Instruction Manual March 2014 6 2 This page intentionally left blank...
Страница 165: ...IMPULSE G Mini Advanced Parameter Listing A p p e n d i x A...
Страница 166: ...IMPULSE G Mini Advanced Instruction Manual March 2014 A 2 This page intentionally left blank...
Страница 190: ...IMPULSE G Mini Advanced Instruction Manual March 2014 A 26 This page intentionally left blank...