DL8 USERS
MANUAL EM-7691-B Rev.24
17.7 WEB SERVER
PROBLEM
CHECK
TO DO
Intranet sites are
not displayed cor-
rectly.
Are the intranet sites displayed in
Compatibility View?
Uncheck the "Display intranet sites in Compatibility View" option
of your browser.
Unable to control
DO or AO on the
browser view
Have you not log on with the
monitor-only ID & password?
Log on with the general ID & password.
(Refer to Section 8.9.)
Is the control on browser setting
for the channel enabled?
Enable “control on browser” setting for the channel.
(Refer to Section 7.6.2.)
Is the channel No. assigned for
I/O mapping?
Channel assigned for I/O mapping cannot be manually con-
trolled. Remove the setting.
(Refer to Section 13.)
17.8 MODBUS/TCP SLAVE
PROBLEM
CHECK
TO DO
Unable to connect
with DL8 from the
Modbus master
side.
Is the Modbus/TCP slave function
enabled?
Enable the Modbus/TCP slave function.
(Refer to Section 14.2.)
Unable to read
data.
Are the register type and the ad-
dress of the channel correct?
Check the register type and the address.
(Refer to Section 14.2.)
Unable to connect
via the router.
Is the port address 502 of the
router used for Modbus/TCP
open?
Set the IP address and the port address 502 of DL8 manually in
the NAT setting of the router.
(Refer to the instruction manual of the router.)
17.9 MODBUS/TCP MASTER
PROBLEM
CHECK
TO DO
DL8 is unable to
connect to Modbus
slave devices.
Isn’t the LAN cable disconnected
or removed from a hub?
Connect the LAN cable firmly. Check the connection lamp of
the hub.
Is the IP address set to DL8
manually?
Set the IP address manually. (Refer to Section 4.3.)
Do DL8 and the Modbus slave
devices have the same network
address?
Check the network address.
e.g.
DL8: 192.168.0.1
slave: 192.168.0.2
Subnet mask: 255.255.255.0
Do the IP addresses of the slave
devices coincide with those regis-
tered with DLCFG?
Check the IP addresses. (Refer to Section 7.2.1.2.)
Are the IP addresses of the slave
side set?
Set the IP addresses of the slave devices.
In using M-System’s remote I/O modules, cycle the power after
setting the IP address. (Refer to the instruction manual of each
I/O module to set the IP address.)