56
DL8 USERS
MANUAL EM-7691-B Rev.24
(3) After configuration is completed, click [OK] to temporarily save the settings.
1.Click
7.4.4 ALARM OUTPUT (TYPE B, C, D & E)
A specific DO can be turned on or off when the input signal enters a signal zone.
(1) Click [Alarm zone setting] button in “PI” configuration dialog to open “Alarm zone setting (PI)” dialog.
Clicking [Alarm output] button for specified zone opens the “Alarm output” list.
Double click a DO channel to set ON/OFF operation.
1.Click
8.Click
3.Double-click
6.Click
PI Configuration Dialog
Alarm zone setting (PI)
Alarm output
7.Click
2.Click
5.Click
4. Select OFF/ON
(2) Click [OK] button to temporarily save the setting.
NOTE
• This function is not available for Type A.
• DO setting must be finished in advance. (Refer to 7.5 DISCRETE OUTPUT (DO).)
• When alarm output turns on a DO, the ON status is maintained while input value is in the zone.
• DO controlled by web server or Modbus/TCP server, is operated in OR logic against the alarm output.
• When alarm output is not used, set it to OFF.
7.4.5 COPYING CH CONFIGURATION
CH configuration of one channel can be copied to another. Refer to 7.2.5 COPYING CH CONFIGURATION.