7.6.2 BASIC SETTING
After channel assignment, configure basic settings for each channel. Click [OK] to temporarily save the settings.
1.Click
PARAMETER
DESCRIPTION
CH name
Enter the name for channel (max. 32 characters).
CH comment
Enter comment regarding channel and tag name (max. 64 characters).
Control on browser
Enable or disable controlling of individual AO channel on the browser view.
Upper/lower limit divided by Scaling must be within the range from -32768 to 32767.
(Fraction is rounded off.)
Operational range on browser Output can be limited within a specific range when it is controlled on the browser view.
Specify upper and lower limits.
Scaling
Set a weight to convert into 16-bit output data (-32768 to 32767).
Output data = Engineering unit value ÷ Scaling (Fraction is rounded off.)
(-10,000,000,000 to -0.0001, 0.0001 to 10,000,000,000)
Number of decimal places
Set number of decimal places of the value displayed on the web browser.
Selectable within 0 to 3.
Engineering unit
Set engineering unit of the engineering unit value.
Input within 16 characters.
Initial value
Set the initial output value used when the cold start mode is specified.
Specify Output data value (Engineering value ÷ Scaling) (-32768 to 32767).
(Refer to 7.7 START MODE.)
7.6.3 COPYING CH CONFIGURATION
CH configuration of one channel can be copied to another. Refer to 7.2.5 COPYING CH CONFIGURATION.