65
DL8 USERS
MANUAL EM-7691-B Rev.24
7.5.2 BASIC SETTING
After channel assignment, configure basic settings for each channel. Click [OK] to temporarily save the settings.
1.Click
PARAMETER
DESCRIPTION
CH name
Enter the name for channel (max. 32 characters).
CH comment
Enter comment regarding channel and tag name (max. 64 characters).
Invert logic
When ON/OFF of output signal and ON/OFF for application signal are reversed, put a check
mark into check box.
Control on browser
Enable or disable controlling of individual DO channel on the browser view.
Initial value
Set the initial output value used when ‘cold start’ mode is specified. (Refer to 7.7 START MODE.)
Status
(ON)
(OFF)
• Display comment
Set text strings corresponding to ON/OFF, respectively (max. 16 characters).
• Color
Set respective colors for ON and OFF to show the status on the web browser.
• Event log
Set whether or not to record in the event log view of web browser when the input state changes.
To record put a check mark in the check box.
7.5.3 COPYING CH CONFIGURATION
CH configuration of one channel can be copied to another. Refer to 7.2.5 COPYING CH CONFIGURATION.
7.5.4 OUTPUT LOGIC
DO is operated by control output, alarm output or I/O mapping output.
I/O mapping assignment prevails other DO assignment (Type: D & E). A channel that I/O mapping combination is not as-
signed is operated in OR logic among the control output and the alarm output.
DO
OR
Control Output (valid at control edge)
•
Control on the browser view
•
Control by Modbus/TCP slave function
•
E-mail delivery success (Type B, C
, D
& E)
•
E-mail delivery failure (Type B, C, D & E)
Alarm Output (valid by signal level or status)
•
AI/PI zone limit alarm (Type B, C, D & E)
•
DI status change
DI count achieving event count
(Type B, C, D & E)