51
DL8 USERS
MANUAL EM-7691-B Rev.24
(3) Choose “SLMP” under “CH setting” and enter “Slave No.,” “SLMP device,” and “SLMP device No.”.
1. Select “SLMP”
2. Enter “Slave No.,” “SLMP device,”
and “SLMP device No.”
PARAMETER
DESCRIPTION
Slave No.
Enter slave No. (0 to 11) set in (1).
SLMP device
Choose the device from the pull-down list.
SLMP device No.
Set the device number for the SLMP device.
The input field of either "SLMP device No. (Decimal)" or "SLMP device No. (Hexadecimal)"
will be active depending on the selected SLMP device.
Invert
When upper and lower registers are not inverted, leave “Invert” check box blank.
(4) Set parameters according to the table below.
PARAMETER
DESCRIPTION
Measuring mode
(SLMP)
Set the type of 32-bit data read from SLMP devices. Choose from below.
• Accumulation
The difference from the time at start and time at reset is accumulated for every sam-
pling.
This corresponds counter data of SLMP devices.
When pulse input module is used choose this.
• Engineering unit value
Signed 32-bit integer value of data such as power data from SLMP devices is identified
and used as sampling data as it is.
• Floating point
Floating point value (single precision floating type) is identified and used as sampling
data as it is. (display range: ±10,000,000,000.000)
• Pulse range
Set the same pulse range which is set at SLMP device.
For detailed information, refer to the manuals for respective SLMP devices.