38
DL8 USERS
MANUAL EM-7691-B Rev.24
7.3 DISCRETE INPUT (DI)
7.3.1 ASSIGNING I/O SIGNALS
A maximum of 64-point discrete inputs (DI1 to DI64) can be monitored.
Assign discrete inputs of I/O modules and/or remote I/Os connected to the DL8, following the procedure below.
7.3.1.1 ASSIGNING I/O MODULE TO DI
(1) Click [Discrete input (DI)] button in “Input/Output” menu to open “Discrete input (DI)” list.
Double-click a row of the DI channel to configure to open the DI configuration dialog.
Input/Output
Discrete input (DI)
DI Configuration dialog
2.Double-click
1.Click
(2) Choose “I/O module” under “CH setting” and assign “Module address” and enter “CH No.” (Refer to 5. CONNECTING
1. Select “I/O module”
2. Enter “Module address” and “CH number”