Mounting of the Subrack
....................................................................................................................................................................................................................................
Procedure
............................................................................................................................................................
1
Install the rack frame according to the configuration.
............................................................................................................................................................
2
Mount the Fiber assembly duct according the configuration (examples
see Appendix B, “Site Configurations”).
Reference:
Rack frame type:
•
Depth 600mm “Fiber Assembly Cable Ducts (600mm)”
(2-17)
•
Depth 300mm “Fiber Assembly Cable Ducts (300mm)”
(2-16)
............................................................................................................................................................
3
Slide the entrance of the cable duct to the correct configuration
position.
300mm depth rack frames:
•
“Cable Duct Position 2200mm Bottom Access (300mm)” (B-9)
•
“Cable Duct Position 2600mm Bottom Access (300mm)” (B-10)
600mm depth rack frames:
•
“Cable Duct Position 2200mm Top Access (600mm)” (B-7)
•
“Cable Duct Position 2200mm Bottom Access (600mm)” (B-8)
•
“Cable Duct Position 2600mm Top Access (600mm)” (B-4)
•
“Cable Duct Position 2600 Bottom Access (600mm)” (B-5)
............................................................................................................................................................
4
Unpack the subrack and check that all the installation materials have
been delivered, see “Subrack Accessories” (1-11).
............................................................................................................................................................
5
Remove the front cover by unlocking the screws and then lifting the
cover temporarily.
Install the correct mounting brackets according the used rack frame
•
see “Mounting Brackets, ETSI/MADM Rack” (2-5).
•
see “Mounting Brackets, 19 Inch Rack” (2-7).
Important!
Store this cover in a protected area.
Installation
....................................................................................................................................................................................................................................
2 - 2
Lucent Technologies - Proprietary
See notice on first page
365-312-761
Issue 1, May 2004