EMC/ESD Safety Information
....................................................................................................................................................................................................................................
The system was developed in compliance with the ETSI Mesh Ground
requirements.
This means that EMC compliance and personnel safety can be
achieved only if the system is connected to a System-Reference
Potential Plane (SRPP) at many places as described in ETS 300 253.
See the figure below.
All peripheral equipment to be connected to the system must also be
connected to the SRPP by one or more fixed wires.
The Protective Earth/Ground of the peripheral equipment must be
connected to the SRPP.
The EMC/ESD boundary is defined at subrack level. The principle is
based on the “Faraday Cage” theory. If there are covers, then the
covers must be closed.
There is an ESD ground/earth socket on the subrack.
A grounded wrist strap with banana plug must be worn when opening
the subrack covers.
This guide describes equipment that contains static sensitive devices.
General information
....................................................................................................................................................................................................................................
365-312-761
Issue 1, May 2004
Lucent Technologies - Proprietary
See notice on first page
1 - 3