9. Object Dictionary
9-24
2
W04
Software Position Limit
3 W08
-
4 W10
Operation
overload
5 W20
Abnormal combination of drive and motor, abnormal
I/O setting
6 W40
Low
voltage
7
W80
Emergency signal input
8~14 -
-
15
STO
STO not connected Statusword fault bit set
0x2015
U Phase Current Offset
ALL
Variable
type
Setting range
Initial
value
Unit
Accessibility
PDO
assignment
Change
attribute
Storage
INT
-1000 to 1000
0
0.1%
RW
No
Always
Yes
Manually set the U phase current offset. The configured offset value is subtracted from the measured
current value, and then applied as an actual current value. Do not manually set the offset if you do not
know the exact setting value. You can check the automatically-tuned value if you tune the current offset
with the procedure function (refer to the description of 0x2700).
0x2016
V Phase Current Offset
ALL
Variable
type
Setting range
Initial
value
Unit
Accessibility
PDO
assignment
Change
attribute
Storage
INT
-1000 to 1000
0
0.1%
RW
No
Always
Yes
Manually set the V phase current offset. The configured offset value is subtracted from the measured
current value, and then applied as an actual current value. Do not manually set the offset if you do not
know the exact setting value. You can check the automatically-tuned value if you tune the current offset
with the procedure function (refer to the description of 0x2700).
0x2017
W Phase Current Offset
ALL
Variable
type
Setting range
Initial
value
Unit
Accessibility
PDO
assignment
Change
attribute
Storage
INT
-1000 to 1000
0
0.1%
RW
No
Always
Yes
Manually set the W phase current offset. The configured offset value is subtracted from the measured
current value, and then applied as an actual current value. Do not manually set the offset if you do not
know the exact setting value. You can check the automatically-tuned value if you tune the current offset
with the procedure function (refer to the description of 0x2700).
For a drive with small to medium capacity (7.5 KW or less), this parameter is not used since the W
phase current is not separately measured.
Содержание XDL-L7NH Series
Страница 2: ......
Страница 12: ......
Страница 21: ...1 Product Configuration 1 9 1 3 2 Servo Motor Parts 80 Flange or below 130 Flange or higher ...
Страница 43: ...2 Wiring and Connection 2 21 ...
Страница 52: ...2 Wiring and Connection 2 30 2 6 5 EnDat 2 2 Encoder Signaling Unit Wiring Servo Motor Encoder Servo Drive ...
Страница 58: ......
Страница 68: ......
Страница 75: ...4 CiA402 Drive Profile 4 7 Internal Block Diagram of CSP Mode ...
Страница 78: ...4 CiA402 Drive Profile 4 10 Internal Block Diagram of PP Mode ...
Страница 86: ...4 CiA402 Drive Profile 4 18 Internal Block Diagram of PV Mode ...
Страница 118: ...5 Drive Application Functions 5 10 ...
Страница 148: ......
Страница 283: ...10 Product Specifications 10 23 SGP Series APM SGP110G ...
Страница 284: ...10 Product Specifications 10 24 SGP Series APM SGP150G ...
Страница 288: ...10 Product Specifications 10 28 FGP Series APM FGP110G ...
Страница 294: ...10 Product Specifications 10 34 XDL L7NHB150U Weight 15 5 kg including the cooling fan ...
Страница 336: ...13 Appendix 13 20 5 Turn on the power again and verify if the firmware is updated ...
Страница 345: ...13 Appendix 13 29 Check firmware version The firmware version is lower than current one can t be downloaded ...
Страница 346: ......