DC brake at a stop
8.1.3
Group
Code
Parameter Name
Setting
Range Default
Unit
Function
group 1
F12
[DC Brake start voltage]
-
0 - 200
50
%
I/O group
I19
[Multi-function Input
terminal P3 Function
select]
11
0 - 25
2
F12: It sets the level as a percent of H33
– [Motor rated current].
Select a terminal to issue a command of DC brake at a stop among P1 to P4.
If P3 terminal is set for this function, set I19 to 11 {DC brake during stop}.
If excessive DC Brake voltage is set or DC Brake time is set too long, it may cause motor
overheating and damage to the motor.