Protective functions
172
10.11 Pipe Broken
Pipe Broken is a safety function to stop when it has detected a broken pipe during
operation. Broken pipe can be detected by an abnormal drop of feedback which will
cause max. speed operation to compensate the feedback drop.
The drive provides broken-pipe protection that will trip (shut off) the drive in this incident.
The setting can be done when the Feedback maintains below A39_Pipe Broken Level
and Output frequency maintains over A41_Pipe Broken Freq. for the time set at
A40_Pipe Broken Delay.
Group
Code
Parameter Name
Setting
Range
Default Unit
Application
group
A38
Pipe Broken Sel
-
Yes/No
No
A39
Pipe Broken Level
-
0-100.0
0.0
%
A40
Pipe Broken Delay
-
0-60.0
10.0
sec
A41
Pipe Broken Freq
-
0-Max Freq.
49.00
Hz
I/O group
I54-
55
Relay Define x
-
20. Pipe Broken 0
►
A38: Sets the Pipe Broken function.
►
A39: Sets the Pipe Break Detection level.