Protective functions
161
Pro
tectiv
e
Fun
ctio
ns
10.2 Overload Warning and trip
Overload warning
10.2.1
Group
Code
Parameter Name
Setting Range Default
Unit
Function
group 1
F54
[Overload warning level]
-
30 - 150
110
%
F55
[Overload warning time]
-
0 - 30
10
Sec
I/O group
I54
[Multi-function relay1 select] 5
0 - 27
12
I55
[Multi-function relay2 select]
5
17
Select one output terminal for this function between Relay1 and Relay2.
If selecting Relay1 as output terminal, set I54 to 5 {Overload: OL}
►
F54: Set the value as a percent of motor rated current.
Overload trip
10.2.2
Group
Code
Parameter
Set
Range Default
Unit
Function
group 1
F56
[Overload trip select]
1
0 - 1
1
F57
[Overload trip level]
-
30 - 200
120
%
F58
[Overload trip time]
-
0 - 60
60
sec
Set F56 to 1.
Inverter output is turned off when motor is overloaded.
Inverter output is turned off when excessive current flows to the motor for F58
–
[Overload trip time].
www.barghmaher.ir
Содержание iG5H Series
Страница 13: ...www barghmaher ir ...
Страница 22: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O www barghmaher ir ...
Страница 23: ...10 Installation Wiring www barghmaher ir ...
Страница 50: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern www barghmaher ir ...
Страница 173: ...Protective functions 160 www barghmaher ir ...
Страница 219: ...206 DECLARATION OF CONFIRMITY www barghmaher ir ...
Страница 223: ...210 www barghmaher ir ...
Страница 225: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 www barghmaher ir ...