Basic Functions
74
►
I6 - I10: Setting input range and corresponding frequency to 0 - +10V V1 input voltage
Ex) when minimum (+) input voltage is 2V with corresponding frequency 10Hz and Max
voltage is 8V with run freq.
Frequency setting via 0 - 10 [V] input or Terminal
7.1.4
Potentiometer
Group
Code
Parameter Name
Setting
Range
Default
Unit
Drive group
0.00
[Frequency Command]
-
0 -400
0.00
Hz
Frq
[Frequency Mode]
3
0 - 8
0
I/O group
I 6
[Filter time constant for V1 input] 10
0 - 9999
10
I 7
[V1 input Min voltage]
-
0 - 10
0
V
I 8
[Frequency corresponding to I 7] -
0 - 400
0.00
Hz
I 9
[V1 input max voltage]
-
0 - 10
10
V
I10
[Frequency corresponding to I 9] -
0 - 400
60.00
Hz
Select 3 in Frq code of Drive group.
0-10V can be directly applied from an external controller or a potentiometer connected
on terminals VR, V1 and CM.