Advanced functions
118
8.13 Relay On/Off Control
If the analog input value is over the set value, the output relay or multi-function output
terminal can be turned ON or OFF. Select the analog input to use for ON/OFF control at
F72 and set the levels at which the output terminal is ON and OFF at F73, 74 respectively. If
the analog input value is over the value set at F73, the output terminal is ON and if below
F74, it is OFF.
Group
Code
Parameter Name
Setting
Range
Default Unit
Function
group 1
F72
OnOff Ctrl Src
-
0: None
1: V
2: I
0
F73
On-Ctrl Level
-
0.00-100.00[sec]
90.00
sec
F74
Off-Ctrl Level
-
0.00-100.00[sec]
10.00
sec
I/O
group
I54-55 Relay Define x
-
19. OnOffControl
0.00
8.14 Power On Run Delay
After Run command is applied by the terminals, the inverter will operate after the time
set in F06_Power-on run has exceeded.
This function can be applied for lubrication purpose in applications such as mining or
oil systems.
Group Code
Parameter Name
Setting
Range
Default Unit
Function
group 1
F5
Power On Run
-
0 : NO
1 : YES
0 : NO
F6
Run Delay Time
-
0-6000[sec]
0
sec
www.barghmaher.ir
Содержание iG5H Series
Страница 13: ...www barghmaher ir ...
Страница 22: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O www barghmaher ir ...
Страница 23: ...10 Installation Wiring www barghmaher ir ...
Страница 50: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern www barghmaher ir ...
Страница 173: ...Protective functions 160 www barghmaher ir ...
Страница 219: ...206 DECLARATION OF CONFIRMITY www barghmaher ir ...
Страница 223: ...210 www barghmaher ir ...
Страница 225: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 www barghmaher ir ...