RS485 communication
184
Note
Note 1) The changed value in Common area affects the current setting but returns to the
previous setting when power is cycled or Inverter is reset. However, changing value is
immediately reflected in other parameter groups even in the case of Reset or Power
On/Off.
Note 2) S/W version of Common area is displayed in Hexadecimal, while that of
parameter area is displayed in decimal.
Note 3) User can register up to Read address 8 ea/Write address 8 ea of discontinuous
addresses and read/write them n data(s) with one Read/Write command. Input/Output
group I66 through I73 are registered in the common read addresses 0x0100 through
0x0107 and it can be read the discontinuous n data(s) (less than 8 ea) with a read
command. Input/Output group I74 through I81 are registered in the common write
addresses 0x0108 through 0x010F and it can be written discontinuous n data(s) (less
than 8 ea) with a write command.
2) Extended Common Area :
2.1) Inverter Monitoring Area Parameters (Reading Only)
Address
Parameter
Scale Unit
Allotment for Bits
0x0300
Inverter Model
-
-
iG5H : 0x000A
0x0301 Inverter capacity
-
-
0.4kW : 0x0019
0.75kW : 0x3200
1.5kW :
0x4015
2.2kW : 0x4022
3.7kW : 0x4037
4.0kW :
0x4040
5.5kW : 0x4055
7.5kW : 0x4075
Reserved
Reserved
Reserved
Reserved
0x0302
Inverter input
voltage /power
supply type
(1-phase, 3-
phase)
/ cooling method
-
-
200V single phase open air cooling : 0x0220
200V 3 phase open air cooling : 0x0230
200V single phase forced cooling : 0x0221
200V 3 phase forced cooling : 0x0231
400V single phase open air cooling : 0x0420
400V 3 phase open air cooling : 0x0430
400V single phase forced cooling : 0x0421
400V 3 phase forced cooling : 0x0431
0x0303
S/W version
-
-
(Ex) 0x0023 : Version 2.3
0x0305
Inverter
operating status
-
-
B15, B14, B13, B12 :
0 : Normal status, 8 : Fault status
B11, B10, B9, B8 : Reserved
B7, B6, B5, B4 :
1 : Speed search, 2 : Accelerating
3 : Steady speed, 4 : Decelerating
5 : Decelerating stop 6 : H/W OCS
7 : S/W OCS 8 : Dwell operating
B3, B2, B1, B0 :
www.barghmaher.ir
Содержание iG5H Series
Страница 13: ...www barghmaher ir ...
Страница 22: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O www barghmaher ir ...
Страница 23: ...10 Installation Wiring www barghmaher ir ...
Страница 50: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern www barghmaher ir ...
Страница 173: ...Protective functions 160 www barghmaher ir ...
Страница 219: ...206 DECLARATION OF CONFIRMITY www barghmaher ir ...
Страница 223: ...210 www barghmaher ir ...
Страница 225: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 www barghmaher ir ...