Chapter 8 Table of Functions
8-13
No. Comm.
No.
Function
Display
Name
Setting Range
Initial Value
Shift in
Operation
Control Mode
V/F
SL
VC
SLT
VC
T
gain
47 0h142F PG Slip
Max%
PG operation
maximum sleep
0 ~ 200
100
X
O
X
X
X
X
48
-
ACR P Gain Current control
period P gain
0 ~ 10000
1200
O
X
O
O
O
O
49
-
ACR I Gain Current control
period I gain
120
O
X
O
O
O
O
51 0h1433 ASR Ref
LPF
speed control
period
reference filter
0 ~ 20000 [ms]
0
X
X
O
O
X
X
52 0h1434 Torque Out
LPF
Torque control
period Output filter
0 ~ 2000 [ms]
0
X
X
X
X
O
O
53
0h1435
Torque Lmt
Src
Torque limit
Setting method
0 Keypad-1
0 :Keypad-1
X
X
X
X
O
O
1 Keypad-2
2 V1
3 I1
4 V2
5 I2
6 Int 485
7 Encoder
8 FiedBus
9 PLC
10 Synchro
11 Binary Type
54
Note18)
0h1436
FWD +Trq
Lmt
forward offsetting
Torque limit
0 ~ 200 [%]
180.0
O
X
X
X
O
O
55 0h1437 FWD –Trq
Lmt
forward
regenerative
torque limit
O
X
X
X
O
O
56 0h1438 REV +Trq
Lmt
reverse offsetting
torque limit
O
X
X
X
O
O
57 0h1439 REV –Trq
Lmt
reverse
regenerative
torque limit
O
X
X
X
O
O
* The grey code refers to hidden code, emerging only in case of setting of the code.
Note 16)
CON-23~28, 31~32 are displayed only when DRV-09 (Control Mode) is “Sensorless2” and
CON-20 (SL2 G View Sel) is set as “YES”.
Note 17)
CON-45~47 are displayed when Encoder Board is inserted and Control mode is V/F PG.
Note 18)
CON-54~57 are displayed only when DRV-09(Control Mode) is set as “Sensorless-1, 2”
or “Vector”. The initial value of torque limit will be changed to 150% with the setting of
ADV-74.
Содержание SV0008iS7-2
Страница 20: ...Chapter 1 Basics 1 5 ...
Страница 54: ...Chapter 3 Installation 3 28 ...
Страница 181: ...Chapter 8 Table of Functions 8 46 ...
Страница 195: ...Chapter 9 Peripheral Devices 9 14 TYPE 2 Maximum 600 Watt TYPE 3 4 5 A ...