Chapter 8 Table of Functions
8-28
8.1.8 Parameter mode – Applied function group (
APP)
No. Comm.
No.
Function
Display
Name
Setting Range
Initial
Value
Shift in
Opera-tion
Control Mode
V/F
SL VC
SLT
VC
T
00
-
Jump Code jump code
0 ~ 99
20
O
O
O
O
O
O
01 0h1801 App Mode applied function selection
0 None
0:
None
X
O
O
O
X
X
1 Traverse
2 Proc PID
3 Reserved
4 Auto Sequence
08
Note28)
0h1808 Trv Apmlit % traverse operating range
0 ~ 20 [%] 0.0
O
O
O
O
X
X
09 0h1809 Trv Scramb % traverse scramble magnitude
0 ~ 50 [%] 0.0
O
O
O
O
X
X
10 0h180A Trv Acc Time traverse accelerating time
0.1 ~ 600.0 [s] 2.0
O
O
O
O
X
X
11 0h180B Trv Dec Time traverse decelerating time
3.0
O
O
O
O
X
X
12 0h180C Trv Offset Hi traverse offset upper limit
0 ~ 20.0 [%] 0.0
O
O
O
O
X
X
13 0h180D Trv Offset lo traverse offset lower limit
0.0
O
O
O
O
X
X
16
Note 29)
0h1810 PID Output PID output monitor
[%]
0.00
-
O
O
O
X
X
17
0h1811 PID Ref Value PID reference monitor
50.00
-
O
O
O
X
X
18 0h1812 PID Fdb Value PID feedback monitor
0.00
-
O
O
O
X
X
19 0h1813 PID Ref Set PID reference setting
-100 ~ 100 [%] 50%
O
O
O
O
X
X
20 0h1814
PID
Ref Source PID reference selection
0 Keypad
0: Key
pad
X
O
O
O
X
X
1 V1
2 I1
3 V2
4 I2
5 Int 485
6 Encoder
7 FieldBus
8 PLC
9 Synchro
10 Binary Type
* The grey code refers to hidden code, emerging only in case of setting of the code.
Note 28)
APP 08~13 codes are displayed only when APP-01 (App Mode) is set as “Traverse”.
Note 29)
APP 16~45 codes are displayed only when APP-01 (App Mode) is set as “Proc PID” or
APP-01(App Mode) is set as “MMC” and Requl Bypass(APO-34) is set as “No”.