background image

Chapter 7 Checking and Troubleshooting   

 

7-11

 

 

 

 

 

7.1.5 Daily and regular checkup list 

 

LS  Inverter,  SV-iS7,  is  an  industrial  electronic  product  that  adopts  up-to-date 

semiconductor device. It may have a failure caused by the ambient environment such 

as temperature, humidity, vibration, etc. or an excessive use of the component over its 

duration. It requires a routine checking to prevent such failure in advance. 

 

     

CAUTION 

 

 

Before starting the maintenance work, the operator must check out the 

power input of the inverter. 

 

Large-capacity  electrolytic  condenser  in  the  power  electronic  circuit 

remains charged with power even after the power is off. So be sure to 

start the maintenance work after you acknowledged the power has been 

completely discharged using a proper tester. 

 

Be sure to use a rectifier type volt meter to obtain an accurate voltage 

when directly measuring the output voltage of inverter. General volt meter 

or  digital  volt  meter  may  result  in  spurious  operation  or  indicate wrong 

value due to high frequency PWM output voltage of the inverter. 

 

If the inverter has not been operated for a long time, capacitors lose their 

charging characteristics and are depleted. To prevent depletion, turn on 

the product once a year and allow the device to operate for 30-60 min. 

Run the device under no-load conditions. 

 

(1) Checking Points 

Electronic product is not intended for a permanent use. When it exceeds the duration 

even under the normal service environment, the product may have trouble in its 

operation due to change in the nature of the parts. To prevent such circumstance, it 

requires a routine and regular checking. 
Especially if you use it under the following environment, have it checked with a shorter 

interval than the regular checking. 

  When the temperature is relatively high in the installed place 

  When the product is operated with a frequent start and stop 

  When the input AC power and load vary seriously 

  When it has severe vibration or shock 

  When there is corrosive gas, combustible gas, oil sludge, dust, salts, metal powder, etc 

 
 

Содержание SV0008iS7-2

Страница 1: ...h symbol in this manual and on your equipment is as follows Symbol Meaning This is the safety alert symbol Read and follow instructions carefully to avoid dangerous situation This symbol alerts the user to the presence of dangerous voltage inside the product that might cause harm or electric shock After reading this manual keep it in the place that the user always can contact easily This manual sh...

Страница 2: ...not subject the cables to scratches excessive stress heavy loads or pinching Otherwise you may get an electric shock CAUTION Install the inverter on a non flammable surface Do not place flammable material nearby Otherwise fire could occur Disconnect immediately the input power if the inverter gets damaged Otherwise it could result in a secondary accident and fire After the input power is applied o...

Страница 3: ... The direction of installation should be observed properly as criterions specified in this manual show Make sure that you should not put screw metal material water oil and the inflammable something else Keep in mind that inverter is very vulnerable to drop from the mid air and strong shock Don t let the inverter exposed to rain snow fog dust etc Do not cover nor block the ventilating system having...

Страница 4: ...ng the inverter body Do not connect phase leading capacitors surge filter radio noise filter to the output of inverter Output terminals terminals named U V W respectively should be connected in a proper phase sequence Make sure that there is not any short circuit terminal wrong wiring It may cause spurious operation or failure Refrain from using a cable other than the cable shielded when you conne...

Страница 5: ...ter restarts if alarm condition is cleared while FX RX signal is on Therefore be sure to operate the alarm reset switch after checking if FX RX signal is off Never modify the inverter for inappropriate use When a magnetic contactor is installed on the power source do not frequently start or stop using this magnetic contactor It may cause the failure of inverter Noise filter should be used for the ...

Страница 6: ...utput Mishandling may cause damage to the inverter Be sure to handle the inverter and option care in the order recommended in the Electro Static Discharge ESD Countermeasure Mishandling may lead to damage to the circuit on the PCB caused by ESD Countermeasure against malfunction troubles If inverter is damaged and then gets into uncontrollable situation the machine may lead to the dangerous situat...

Страница 7: ...tion do not clean LCD display etc using detergent or alcohol Storage Be sure to keep the inverter under the following conditions if you don t use it for a long period of time Make sure that you satisfy the recommended storage environment See page v If the storage period exceeds 3 months be sure to keep it at the ambient temperature of 10 30 C to prevent Deterioration by Temperature of electrolytic...

Страница 8: ...tems which should be learned before using the Inverter 2 Specifications The control specifications ratings and types of the input and output 3 Installation Information on the use environment and installation method 4 Wiring Wiring information for the power supply and signal terminals 5 How to Use Keypad Descriptions on the display and operation keys on the main body of the Inverter 6 Basic Functio...

Страница 9: ...livered to the end user and mainte nance manager Option Module Guide The following Option Module Guides will be provided when you purchase the applicable Option Module In addition if you access our homepage http www lsis com Support Service Down load Center you can download it in PDF file IS7 PLC Card Option Module Guide IS7 Encoder Card Option Module Guide IS7 Profibus DP Card Option Module Guide...

Страница 10: ...moved less than 75kW 1 3 1 2 3 End product more than 90kW 1 4 1 2 4 When the front cover is removed more than 90kW 1 4 Chapter 2 Specifications 2 1 Specifications 2 1 2 1 1 Rated Input and Output Input voltage of 200V class 0 75 22kW 2 1 2 1 2 Rated Input and Output Input voltage of 200V class 30 75kW 2 1 2 1 3 Rated Input and Output Input voltage of 400V class 0 75 22kW 2 2 2 1 4 Rated Input and ...

Страница 11: ...ension and Weight of Frame UL Enclosed Type 12 IP54 Type 3 36 3 1 6 Installation Guide UL Enclosed Type12 IP54 Type 3 37 Chapter 4 Wiring 4 1 Wiring 4 1 4 1 1 How to separate front cover when wiring 4 3 4 1 2 How to separate front cover when wiring 90 375 kW 400V 30 75kW 200V 4 5 4 1 3 Built in EMC Filter 4 6 4 1 4 Wiring precaution 4 9 4 1 5 Grounding 4 9 4 1 6 Terminal wiring diagram Power termi...

Страница 12: ... on off connector functionality 4 28 4 1 15 The grounded ON OFF connection removal 4 29 4 2 Operation Checking 4 26 4 2 1 Easy start 4 26 4 2 2 Easy start operation 4 26 4 2 3 Checking for normal working 4 27 Chapter 5 How To Use Keypad 5 1 How To Use Keypad 5 1 5 1 1 Standard KEYPAD appearance and description Graphic keypad 5 1 5 1 2 Menu composition 5 6 5 1 3 Mode shift 5 9 5 1 4 Group shift 5 1...

Страница 13: ...n Power on Run 6 14 6 1 8 Setting of accelerating decelerating time and pattern 6 15 6 1 9 Motor output voltage adjustment 6 19 Chapter 7 Checking and Troubleshooting 7 1 Checking and troubleshooting 7 1 7 1 1 Protective functions 7 1 7 1 2 Alarm functions 7 4 7 1 3 Troubleshooting 7 6 7 1 4 Replacement of cooling fan 7 9 7 1 5 Daily and regular checkup list 7 11 Chapter 8 Table of Functions 8 1 T...

Страница 14: ... 32 8 1 10 Parameter mode Option card function group APO 8 36 8 1 11 Parameter mode Protective function group PRT 8 38 8 1 12 Parameter mode 2nd motor function group M2 8 41 8 1 13 Trip mode TRP Current or Last x 8 42 8 1 14 Config mode CNF 8 42 8 1 15 User Macro mode MC1 8 45 8 1 16 User Macro mode Traverse operation function group MC2 8 46 Chapter 9 Peripheral Devices 9 1 Peripheral Devices 9 1 ...

Страница 15: ...1 1 Classification Product 11 1 11 1 1 Classification Standard 11 1 11 1 2 Classification standard qcquisition 11 1 11 1 3 Classification Model SV iS7 Products 11 1 Chapter 12 Single Phase Rating 12 1 Introduction 12 1 12 2 Power HP Input Current and Output Currnet 12 1 12 3 Input Frequency and Voltage Tolerance 12 1 12 4 Wiring and Peripheral Device 12 1 12 5 Considerations When Using a Three Pha...

Страница 16: ...W 0 75 kW Wide Use Inverter 2 3 Phase 200 230 V 4 3 Phase 380 480 V N NON S GLCD Graphic Loader O OPEN E Enclosed UL Type1note1 P Enclosed ULType 12 Blank Non EMC F EMC Blank Non DCR D DCR R DB Resistor Inner Mounted W Web S Synchro T Safety V Classific ation 0015 2 2 kW 1 5 kW 0022 3 7 kW 2 2 kW 0037 5 5 kW 3 7 kW 0055 7 5 kW 5 5 kW 0075 11 kW 7 5 kW 0110 15 kW 11 kW 0150 18 5 kW 15 kW 0185 22 kW...

Страница 17: ...back cover of the manual 1 1 3 Preparation of device and Parts for operation Preparation for operation might slightly vary Prepare parts according to the use 1 1 4 Installation Make sure you install the product correctly considering the place direction or surroundings in order to prevent decrease in the life and performance of the inverter 1 1 5 Distribution Connect the power supply electric motor...

Страница 18: ... less than 75 kW Front cover Remove it when wiring Keypad Screw to fix the front Wiring bracket Ground terminal Cooling FAN Keypad connection Encoder option Power terminal Wiring bracket Communication option connection PLC extension I O communication option connection I O board and terminal Inverter condition display BAR ...

Страница 19: ...per front cover right side Screw to fix the lower front cover right side Cooling fan Upper front cover Lower front cover Ground Power input Signal input Communication option board connection PLC Extension I O Communication option Connection part Encoder option board Keypad connection terminal I O board and terminal Inverter condition display LED Power Busbar R S T U V W P N Shield plate Main SMPS ...

Страница 20: ...Chapter 1 Basics 1 5 ...

Страница 21: ...tage V 3 phase 200 230 VAC 15 10 Input Frequency 50 60 Hz 5 Rated Current A VT 6 8 10 6 14 9 21 3 28 6 41 2 54 7 69 7 82 9 116 1 CT 4 3 6 9 11 2 14 9 22 1 28 6 44 3 55 9 70 8 85 3 2 1 2 Rated Input and Output Input voltage of 200V class 30 75kW Type SV xxx iS7 2x 0300 0370 0450 0550 0750 1 Motor Applied VT HP 50 60 75 100 120 kW 37 45 55 75 90 CT HP 40 50 60 75 100 kW 30 37 45 55 75 Rated Output 2...

Страница 22: ...9 26 4 35 5 41 1 55 7 CT 2 2 3 6 5 5 7 5 11 0 14 4 22 0 26 6 35 6 41 6 2 1 4 Rated Input and Output Input voltage of 400V class 30 160kW Type SV xxx iS7 4x 0300 0370 0450 0550 0750 0900 1100 1320 1600 1 Motor Applied VT HP 50 60 75 100 120 150 180 225 250 kW 37 45 55 75 90 110 132 160 185 CT HP 40 50 60 75 100 120 150 180 225 kW 30 37 45 55 75 90 110 132 160 Rated Output 2 Rated Capacity kVA 46 57...

Страница 23: ...n 440V The current rating is based on CT current 3 The output of rated current is limited according to setting of the carrier frequency CON 04 4 In case of Sensorless 1 you can set the frequency at up to 300Hz by selecting 3 as the control mode DRV 09 Control Mode In case of Sensorless 2 you can set the frequency at up to 120Hz by selecting 4 as the control mode DRV 09 Control Mode 5 The maximum o...

Страница 24: ... NPN Sink PNP Source selectable Function forward operation reverse operation reset external trip emergency stop jog operation sequential frequency high medium low multi level acceleration and deceleration high medium low D C control during stop selection of a second motor frequency increase frequency decrease 3 wire operation change to general operation during PID operation Main inverter body oper...

Страница 25: ...75 15kW 200 400V class 22kW 400V class Inhalation cooling 22 75kW 200V class 30 375kW 400V class Protection Structure 0 75 22kW 200V 0 75 75kW 400V Open type IP 21 default UL enclosed type 1 Option 3 30 75kW 200V 90 375kW 400V Open type IP 00 default UL enclosed type 1 Option 3 0 75 22kW 2 4 and etc Enclosed IP54 type UL enclosed type 12 Ambient Temperature CT Heavy Duty load 10 50 without ice or ...

Страница 26: ...it capable of delivering not more than 100 kARMS at the drive s maximum rated voltage French Le courant maximum de court circuit présumé autorisé au connecteur d alimentation électrique est défini dans la norme IEC 60439 1 comme égal à 100 kA L entraînement convient pour une utilisation dans un circuit capable de délivrer pas plus de 100 kA RMS à la tension nominale maximale de l entraînement ...

Страница 27: ...nt thermal saturation phenomenon Be sure to check air is circulated in a normal condition Be sure to check motor and drive system are ready to start Electrical Installation Checking List Make sure that the protective grounding is properly done Replace the condenser with new one if it lasted longer than two years Set the input voltage to the nominal input voltage of the inverter Check if the input ...

Страница 28: ...wing allowable temperature In other word the ambient temperature insi de or outside of the panel regardless of the installation needs to be measured a round 5cm of the inverter Measurement Points of Surrounding Temperature Install the inverter on an inflammable surface because its temperature rises high during operation Sufficient space is required to prevent heat saturation because the inverter e...

Страница 29: ...ources and wait for at least 10 minutes French Risque de blessure ou de choc électrique Avant d installer ou d utiliser l appareil vous devez lire attentivement le manuel et suivre les consignes de sécurité Avant d ouvrir le capot débrancher toutes les sources d alimentation et attendre au moins 10 minutes Caution Avoid direct rays of light or a warm and humid place Install the inverter in a close...

Страница 30: ... 4 3 1 2 Exterior and Dimension UL Enclosed Type 1 IP21 Type 1 SV0008 0037iS7 200V 400V mm inches Inverter capacity W1 W2 H1 H2 H3 D1 A B SV0008 0037 iS7 2 4 150 5 90 127 5 00 284 11 18 257 10 11 18 0 70 200 7 87 5 0 19 5 0 19 ...

Страница 31: ...Chapter 3 Installation 3 5 2 SV0055 0075iS7 200V 400V mm inches Inverter capacity W1 W2 H1 H2 H3 D1 A B SV0055 0075 iS7 2 4 200 7 87 176 6 92 355 13 97 327 12 87 19 0 74 225 8 85 5 0 19 5 0 19 ...

Страница 32: ...Chapter 3 Installation 3 6 3 SV0110 0150iS7 200V 400V mm inches Inverter capacity W1 W2 H1 H2 H3 D1 A B SV0110 0150 iS7 2 4 250 9 84 214 6 8 44 385 15 15 355 13 97 23 6 0 92 284 11 18 6 5 0 25 6 5 0 25 ...

Страница 33: ...hapter 3 Installation 3 7 4 SV0185 0220iS7 200V 400V mm inches Inverter capacity W1 W2 H1 H2 H3 D1 A B SV0185 0220 iS7 2 4 280 11 02 243 5 9 58 461 6 18 17 445 17 51 10 1 0 39 298 11 73 6 5 0 25 6 5 0 25 ...

Страница 34: ...Chapter 3 Installation 3 8 5 SV0300 iS7 200V IP00 Type mm inches Inverter capacity W1 W2 W3 H1 H2 H3 D1 A B C SV0300 iS7 2 300 11 81 190 7 48 570 22 44 552 21 73 10 0 39 265 2 10 44 10 0 39 10 0 39 M8 ...

Страница 35: ...ter 3 Installation 3 9 6 SV0370 0450iS7 200V IP00 Type mm inches Inverter capacity W1 W2 W3 H1 H2 H3 D1 A B C SV0370 0450 iS7 2 370 14 56 270 10 63 630 24 8 609 23 97 11 0 43 281 2 11 07 10 0 39 10 0 39 M10 ...

Страница 36: ... SV0300 0450iS7 400V mm inches Inverter capacity W1 W2 H1 H2 H3 D1 D2 A B C SV300 450 iS7 4 300 1 11 81 242 8 9 55 594 1 23 38 562 22 12 24 1 0 9 4 DCR Type 10 0 39 10 0 39 M8 303 2 11 93 161 6 33 Non DCR Type 271 2 10 67 129 5 78 ...

Страница 37: ...r 3 Installation 3 11 8 SV0550 0750iS7 200V IP00 Type mm inches Inverter capacity W1 W2 W3 H1 H2 H3 D1 A B C SV0550 0750 iS7 2 465 18 3 381 15 0 750 29 52 723 5 28 48 15 5 0 61 355 6 14 0 11 0 43 11 0 43 M16 ...

Страница 38: ...550 0750iS7 400V mm inches Inverter capacity W1 W2 H1 H2 H3 D1 D2 A B C SV0055 0075 iS7 4 370 1 14 57 312 8 12 31 663 5 26 12 631 4 24 85 24 1 0 94 DCR Type 10 0 39 10 0 39 M8 373 3 14 69 211 5 8 32 Non DCR Type 312 4 12 29 150 6 5 92 ...

Страница 39: ...stallation 3 13 10 SV0900 1100iS7 400V IP00 Type mm inches Inverter capacity W1 W2 W3 H1 H2 H3 D1 A B C SV0900 1100 iS7 4 510 20 07 381 15 0 350 13 77 783 5 30 84 759 29 88 15 5 0 61 422 6 16 63 11 0 43 11 0 43 M16 ...

Страница 40: ...nstallation 3 14 11 SV1320 1600iS7 400V IP00 Type mm inches Inverter capacity W1 W2 W3 H1 H2 H3 D1 A B C SV1320 1600 iS7 4 510 20 07 381 15 0 350 13 77 861 33 89 836 32 93 15 5 0 61 422 6 16 63 11 0 43 11 0 43 M16 ...

Страница 41: ...stallation 3 15 12 SV1850 2200iS7 400V IP00 TYPE mm inches Inverter capacity W1 W2 W3 H1 H2 H3 D1 A B C SV1850 2200iS7 4 690 27 16 581 22 87 528 20 79 1078 42 44 1043 5 41 08 25 5 1 00 450 17 72 14 0 55 15 0 59 M20 ...

Страница 42: ...er 3 Installation 3 16 13 SV2800iS7 400V IP00 TYPE mm inches Inverter capacity W1 W2 W3 H1 H2 H3 D1 A B C SV2800iS7 4 771 30 35 500 19 69 500 19 69 1138 44 80 1110 43 70 15 0 59 440 17 32 13 0 51 13 0 51 M16 ...

Страница 43: ...stallation 3 17 14 SV3150 3750iS7 400V IP00 TYPE mm inches Inverter capacity W1 W2 W3 H1 H2 H3 D1 A B C SV3150 3750iS7 4 922 36 30 580 22 83 580 22 83 1302 5 51 28 1271 5 50 06 15 0 59 495 19 49 14 0 55 14 0 55 M16 ...

Страница 44: ...18 3 1 3 External dimension UL Enclosed Type12 IP54 Type 1 SV0008 0037iS7 200V 400V mm inches Inverter capacity W1 W2 H1 H2 H3 D1 A B SV0008 0037 iS7 2 49 204 2 8 03 127 5 0 419 16 49 257 10 11 95 1 3 74 208 8 18 5 0 19 5 0 19 ...

Страница 45: ...Chapter 3 Installation 3 19 2 SV0055 0075iS7 200V 400V mm inches Inverter capacity W1 W2 H1 H2 H3 D1 A B SV0055 0075 iS7 2 4 254 10 0 176 6 92 460 6 18 13 327 12 87 88 1 3 46 232 3 9 14 5 0 19 5 0 19 ...

Страница 46: ...ter 3 Installation 3 20 3 SV0110 0150iS7 200V 400V mm inches Inverter capacity W1 W2 H1 H2 H3 D1 A B SV0110 0150 iS7 2 4 313 1 12 32 214 6 8 44 590 8 23 25 355 13 97 101 7 4 0 294 4 11 59 6 5 0 25 6 5 0 25 ...

Страница 47: ...ter 3 Installation 3 21 4 SV0185 0220iS7 200V 400V mm inches Inverter capacity W1 W2 H1 H2 H3 D1 A B SV0185 0220 iS7 2 4 343 2 13 51 243 5 9 58 750 8 29 55 445 17 51 91 6 3 60 315 5 12 42 6 5 0 25 6 5 0 25 ...

Страница 48: ...iS7 2 4 200 355 225 10 8 4 9 3 7 7 SV0110iS7 2 4 250 385 284 20 17 2 16 8 14 SV0150iS7 2 4 250 385 284 20 17 2 16 8 14 SV0185iS7 2 280 461 6 298 30 27 25 9 22 9 SV0220iS7 2 280 461 6 298 30 25 8 25 9 22 9 SV0300iS7 2 300 570 265 2 29 5 SV0370iS7 2 370 630 281 2 44 SV0450iS7 2 370 630 281 2 44 SV0550iS7 2 465 750 355 6 72 5 SV0750iS7 2 465 750 355 6 72 5 SV0185iS7 4 280 461 6 298 27 4 23 5 23 3 19 ...

Страница 49: ...4 510 861 422 6 114 SV1850iS7 4 690 1078 450 200 SV2200iS7 4 690 1078 450 200 SV2800iS7 4 771 1138 440 252 SV3150iS7 4 922 1302 5 495 352 SV3750iS7 4 922 1302 5 495 352 Note Weight Kg above indicates the total weight including EMC FILTER and DCL excluding box packing 30 through75 kW 200V products don t have an option type 30 through 160kW 400V products have only DCL option type 280 through 375kW 4...

Страница 50: ...37iS7 2 4 204 2 419 208 8 2 7 2 7 7 6 7 SV0055iS7 2 4 254 460 6 232 3 12 8 10 2 12 1 9 5 SV0075iS7 2 4 254 460 6 232 3 12 9 10 3 12 2 9 6 SV0110iS7 2 4 313 1 590 8 294 4 25 6 22 8 22 4 19 6 SV0150iS7 2 4 313 1 590 8 294 4 25 9 23 1 22 7 19 9 SV0185iS7 2 343 1 750 8 315 5 38 3 34 2 34 1 29 9 SV0220iS7 2 343 2 750 8 315 5 38 3 34 2 34 1 29 9 SV0185iS7 4 343 2 750 8 315 5 34 9 31 31 27 1 SV0220iS7 4 ...

Страница 51: ...keypad Release the upper lower screw on the transparent keypad cover and then separate the transparent cover from the inverter Separate the keypad from the inverter 2 How to separate IP54 front cover Loosen the captive screws nine or thirteen depending on the size of the frame around the edge of the cover Remove the cover ...

Страница 52: ...n the corner Mount the inverter onto fixing hole on the panel and securely tighten the four screws or bolts Place the four rubber packings to the each corner 4 Power cable wiring Connects the input output power cable as followed picture Refer to Chapter 4 Wiring for the detailed wiring ...

Страница 53: ... Place the front cover matching with plate hole Securely tighten the screw at the corner of front cover Connect the cable to the keypad and then place the front cover on the inverter Place the transparent keypad cover on the keypad and tighten the upper lower screw ...

Страница 54: ...Chapter 3 Installation 3 28 ...

Страница 55: ...rating of the circuit breaker done properly Is the power wiring input properly to the inverter input terminal If the input power is connected with the input terminal U V W it may cause damage to the inverter Is the motor wiring connected with the inverter output terminal in a proper phase sequence Otherwise the motor will be rotated adversely Is 600V vinyl insulation wire adopted for the power and...

Страница 56: ...s the wiring of the optional devices done properly Aren t there any wiring mis connected Are the inverter control circuit terminal screws fastened tightly Aren t there any wire fragments or screw left Doesn t the remaining wire connected with the terminal contact the terminals nearby Is the control circuit wiring isolated from the main circuit wiring in the duct or control panel Doesn t the length...

Страница 57: ...se fixed volt of the lower end of up cover 1 How to separate Keypad 2 How to assemble plug when connecting Keypad As showing figures below install the keypad after connecting the plug Under pressing the lower end of keypad pull the upper part of keypad Connection wire for Loader when keypad is disconnected ...

Страница 58: ...hen separate keypad Separate the front cover releasing fixed bolt Before wiring IP54 product must be installed on the panel Separate front cover releasing the fixed bolt I O board control circuit Terminal Power circuit terminal Front cover fixed bolt Keypad Keypad fixed cover Wiring hole Built in circulation fan Keypad cover fixed bolt ...

Страница 59: ... 90 375 kW 400V 30 75kW 200V Releasing the right left fixed bolt on the lower front cover and get down the lower front cover and then open it Now you can wire power part R S T P N U V W and signal cable terminal block encoder option communication option PLC option etc ...

Страница 60: ... of on off swich is set to off 1 How to set EMC Filter functions Less than 7 5kW Products EMC filter OFF EMC filter ON 2 How to remove EMC Filter ON OFF connector Less than 7 5kW Product EMC filter ON EMC filter OFF Check the voltage by a tester in 10minute after cutting the power supply In case separate with connector pull the connector while pressing fixed hasp When reinstalling be sure to hook ...

Страница 61: ...ic wave while being used in power source of symmetrical ground method Be sure to use EMC filter in symmetrical ground method such as Y connection Caution Leakage current increases while EMC filter is ON Do not use EMC filter when the input is asymmetrical way such as Delta connection It may cause an electric shock Asymmetrical Ground structure 1 phase is grounded in Delta connection Grounded middl...

Страница 62: ...d the charge lamp for the power terminal are OFF before wiring terminals The charge capacitor may hold high voltage even after the power is disconnected Use caution to prevent the possibility of personal injury 9 Do not connect with MC at output pare of inverter and make MC On Off during operation It can cause the Trip or damage of inverter 10 When using a DC common with 30 75kW product please be ...

Страница 63: ...60 132 220 kW 100 280 315 kW 185 375 kW 240 4 1 6 Terminal wiring diagram POWER terminal block 1 Wiring of Inverter below 7 5kW 2 Wiring of 11 22kW Product R L1 S L2 T L3 P B N U V W 3 Wiring of 30 75kW Product R L1 S L2 T L3 P1 P2 N U V W 3 phase AC input power supply Ground terminal 3Phase AC IM R L1 S L2 N U V W P B 3Phase AC IM T L3 Dynamic brake resistor Motor 전동기 전동기 전동기 External Fuse ...

Страница 64: ...he reverse direction switch the cables at the U and V terminals French Si la commande avant Fx est activée le moteur doit tourner dans le sens anti horaire si on le regarde côté charge du moteur Si le moteur tourne dans le sens inverse inverser les câbles aux bornes U et V Caution English Apply rated torques to the terminal screws Loose screws may cause short circuits and malfunctions Tightening t...

Страница 65: ... de la borne d alimentation et une valeur nominale de 300 V 75 pour le câblage de la borne de commande Les câblages de l alimentation électrique doivent être connectés aux bornes R S et T Leur connexion aux bornes U V et W provoque des dommages internes à l onduleur Le moteur doit être raccordé aux bornes U V et W L arrangement de l ordre de phase n est pas nécessaire ...

Страница 66: ...al of inverter to N terminal of the dynamic braking unit B terminal of inverter is not used R L1 S L2 T L3 P B N U V W Terminal Symbol Terminal Name Description R L1 S L2 T L3 AC power supply input Connects normal AC input P DC voltage terminal DC link voltage terminal N DC voltage terminal DC link voltage terminal P B Dynamic brake resistor Connects dynamic brake resistor U V W Inverter output Co...

Страница 67: ...ttention when using 30 75W product for DC Common Buying DC reactor from the outside it can not be installed with 30 75kW product If you want to use DC reactor of product please purchase type of 30 75kW product mounted with DC reactor P1 terminal is at the Reactor s front end while P2 terminal at its back end In the event of using such other DCR mounted product for DC Common you must use P2 and N t...

Страница 68: ...al Symbol Terminal Name Description R L1 S L2 T L3 AC power supply input Connects normal AC input P1 DC voltage terminal DC link voltage terminal It is located in front of DCL terminal P2 N Dynamic brake unit connection DC common terminal 1 Voltage terminal connecting Dynamic brake unit DC common terminal N DC voltage terminal DC link voltage terminal U V W Inverter output Connects the 3 phase ind...

Страница 69: ... 45 kW M8 61 2 91 8 95 95 2 0 2 0 350A 55 kW M10 89 7 122 0 120 120 3 0 3 0 400A 75 kW M10 89 7 122 0 150 150 4 0 4 0 450A 4 0 0 V 0 75 1 5kW M4 7 1 12 2 5 2 5 14 14 10A 500V 2 2 kW M4 7 1 12 2 5 2 5 14 14 15A 3 7 kW M4 7 1 12 2 5 2 5 14 14 20A 5 5 kW M5 24 5 31 8 4 2 5 12 14 32A 7 5 kW M5 24 5 31 8 4 4 12 12 35A 11 kW M5 24 5 31 8 6 6 10 10 50A 15 kW M5 24 5 31 8 10 10 8 8 63A 18 5 kW M6 30 6 38 ...

Страница 70: ... a particularly long distance motor In addition more than 5 5kW products the settable maximum carrier frequency is shown in Table 2 the maximum carrier frequency according wire length Table 1 Maximum wiring length by inverter capacity Table 2 The maximum carrier frequency according wire length Please apply below according to the installation site because output peak voltage depending on the instal...

Страница 71: ...t of inverter or connect output filters output reactor dv dt filter sine wave filter in order to protect inverter and motor form surge voltage The output voltage with high switching frequency and fast rising time occur the motor shaft current that flow through the motor bearing This motor shaft current corrode surface of the bearing slowly eventually motor burning accident may occur To decrease th...

Страница 72: ... terminal with NPN mode Sink mode and PNP mode Source mode by using NPN Sink PNP Source set terminal Each mode connecting methods are follows 1 NPN mode Sink mode Set NPN Sink PNP Source switch into NPN CM 24V GND is common terminal of contact point input signal Initial set of Factory default is NPN mode Sink mode Inner source 24V CM 24G P1 FX P2 RX NPN PNP NPN mode Sink mode On Off I PTC set term...

Страница 73: ... signal PNP mode Source mode Set NPN Sink PNP Source switch into PNP When use exterior source If you want try to use exterior 24V source connect exterior source terminal with CM 24V GND Inner source 24V 24 24V P1 FX P2 RX PNP mode Source mode When using inner source PNP mode Source mode When using external source External Source 24V CM 24G P1 FX P2 RX NPN PNP NPN PNP ...

Страница 74: ...al Open Open Collector Output 24V power supply Digital contact point input NPN PNP Sink Source mode support In case of analog voltage input with potentiometer 10V 10V input In case of analog current input 0 20 mA input RS485 Port S C2 CM S 5G P4 P3 P2 P1 CM 24 EG Q1 NC A2 AO1 C1 AO2 5G I1 V1 VR VR CM P8 P7 P6 P5 B1 A1 0 10V Output 0 20mA Output 4 20mA Output Relay2 Normal Open Relay1 Normal Open O...

Страница 75: ...port In case of analog voltage input with potentiometer 10V 10V input In case of analog current input 0 20 mA input AO2 0 10V Output S C2 5G S CM P4 P3 P2 P1 CM 24 EG Q1 NC A2 AO1 C1 CM I1 V1 VR VR CM P8 P7 P6 P5 B1 A1 RS485 Port 0 20mA Output 4 20mA Output Relay2 Normal Open Relay1 Normal Open Open Collector Output 24V power supply Digital contact point input NPN PNP Sink Source mode support In c...

Страница 76: ...ltage input for instance the state no voltage is applied to V1 is not 0V but 0V is input to V1 in fact is 0V In case of analog voltage input accurate linear property is shown by Bipolar at the state 10 0 10V input is received while by Unipolar at the state 0 10V input if received Warning If the analog voltage input is interrupted with the frequency reference source at the state of analog voltage i...

Страница 77: ...al and analog voltage and current terminals note In case Basic I O common terminal are different from the CM common terminal Output Signal Analog A01 Multi function analog voltage output terminal Select the one among Output frequency Output current DC voltage Ouput voltage 0 10V Maximum output voltage 10V Maximum output current 10mA A02 Multi function analog current output terminal Select the one ...

Страница 78: ...e Terminal Description S S CM RS 485 signal input terminal RS 485 signal line Refer to Communication Function contained in iS7 User Manual You can download it from LSIS website http www lsis com This provided manual is the simple version of iS7 User Manual ...

Страница 79: ...rent and voltage terminals Q1 Multi function terminal open collector DC26V below 100mA EG Earth terminal for external power supply Earth terminal for open collector 24 External 24V power supply 0 33 1 25 16 22 Maximum output current 150mA CM 24V power supply common terminal Common terminal for 24V power supply A1 Multi function relay 1 output A contact point 0 33 2 0 14 22 Below AC250V 5A Below DC...

Страница 80: ...function 4 1 14 How to remove the front cover and set up on off connector functionality 1 IS7 30 75KW 400V product set up If you use a connection switch off varistors and Y CAP with 30 75KW 400V product be sure to contact our sales team or a customer support team to receive action 2 IS7 90 375KW 400V product set up After removing the keypad release the left right of the fixed bolt at the top of th...

Страница 81: ...Chapter 4 Wiring 4 27 4 1 15 The grounded ON OFF connection removal 1 SV0900 1600iS7 400V 2 SV1850 2200iS7 400V 3 SV2800 3750iS7 400V SCR Snubber Board SCR Snubber Board SCR Snubber Board ...

Страница 82: ...e now 3 Set the motor capacity used EX 0 75KW 1 5KW 4 Set the number of poles of the motor used 5 Set the rated voltage of the motor used Of the set values 0V refers to the voltage equal to the inverter input voltage 6 Set the rated frequency of the motor used 7 Set the inverter input voltage 8 Set the operation command method EX KEYPAD FX RX 1 FX RX 2 etc 9 Set the command frequency EX 50Hz 60Hz ...

Страница 83: ...rce of DRV 06 is 0 Keypad Freq Ref Src of DRV 07 is 0 Keypad 1 and set DRV 01 Cmd Frequency into temporary speed Command forward operation by pressing FWD please At this time shaft of motor at the side of load rotates into counterclock wise direction Otherwise it must be changed 2 terminals among the inverter output terminal U V W Forward direction Operation ...

Страница 84: ...ow to Use Keypad 5 1 5 1 How to Use Keypad 5 1 1 Standard KEYPAD appearance and description Graphic keypad Standard Keypad is used in Inverter parameter setting Monitor display and Inverter operations 1 Dimensions ...

Страница 85: ...e to use saved data previously if press this button before pressing Program Key Move to first code when code moving is required in a group Move to Monitor mode when Mode moving Forward Key Motor rotates Forward direction Reverse Key Motor rotates Reverse direction Stop Reset Key Stop Under operating Trip release when a trip occurs 1 Cancel ESC 13 PROGRAM set 5 Reverse operation 3 MODE selection 11...

Страница 86: ... auto sequence operation Mode Display Operating Frequency command Multi function Key Inverter Operating Status Status Display Item Monitor Mode Display Item 1 Monitor Mode Display Item 2 Monitor Mode Display Item 3 Monitor Mode Cursor MON T K N STP 0 00Hz Mode Display Group Display Multi function Key Setting Inverter Operating Status Status display Item Parameter Value Settable Range Currently Set...

Страница 87: ...uency command P Pulse input frequency command U Frequency command during UP operation Up Down operation D Frequency command during DOWN operation Up Down operation S Frequency command during STOP operation Up Down operation O FBus Option frequency command X V2 I2 frequency command of sub terminal block J Jog frequency command R Internal 485 frequency command 1 9 A F Sequential frequency command 4 ...

Страница 88: ...ard REV Operating reversely DC DC output WAN Warning STL Stalling SPS Speed Search OSS SW OC controlled OSH HW OC controlled TUN Auto Tuning 5 Status Display Items see Operating status monitoring on this chapter 5 1 7 6 Monitor Mode Display Items see Operating status monitoring on this chapter 5 1 7 ...

Страница 89: ...in groups Mode Display Description Monitor mode MON Displays information on the operating status of the inverter Can monitor frequency setting operating frequency display output current and voltage etc Parameter mode PAR Can set functions necessary for operation Divided into a total of 12 groups each suitable for the functional difficulty and objective User and Macro mode U and M You can group onl...

Страница 90: ...celeration time setting and operation command selection etc Basic group BAS Can set the basic functions such as the motor parameter and sequential frequency etc Advanced function group ADV Can set the acceleration deceleration pattern and frequency control function etc Control function group CON Can set functions related to sensorless and vector control Input terminal function group IN Can set fun...

Страница 91: ...roup Display Description User group USR Of the function items of each group of the parameter mode the items that need to be monitored or that are frequently set by the user are grouped and displayed It is registered by using the multi function key of the keypad Macro group MCx The functions necessary for the inverter according to the load type can be grouped and selected at the time of delivery fr...

Страница 92: ...ey once You have shifted to Parameter Mode Press Mode key once You have shifted to Config Mode Press Mode key once You come back to Monitor Mode MON T K N STP 0 00Hz MON T K N STP 0 00Hz PAR DRV N STP 0 00Hz 00 Jump Code 9 CODE 01 Cmd Frequency 0 00 Hz 02 Cmd Torque 0 0 CNF N STP 0 00Hz 00 Jump Code 40 CODE 01 Language Sel English 02 LCD Contrast ...

Страница 93: ...S Press Right key once You shift to Advanced Function Group ADV Press Right Shift key 7 times The group changed in sequence PRT is displayed Press Right Shift key once You come back to the Drive Group DRV of Parameter Group MON T K N STP 0 00Hz PAR ADV N STP 0 00Hz 00 Jump Code 24 CODE 01 Acc Pattern Linear 02 Dec Pattern Linear PAR DRV N STP 0 00Hz 00 Jump Code 9 CODE 01 Cmd Frequency 0 00 Hz 02 ...

Страница 94: ...of Parameter Mode If DRV is not displayed press Mode key until DRV emerges or press ESC once If you press Down key you will shift to code No 0 in DRV of Parameter Mode as shown on the left Press Right key once You shift to BAS of Parameter Mode You can shift the code by using Up or Down key PAR BAS N STP 0 00Hz 00 Jump Code 20 CODE 01 Aux Ref Src None 04 Cmd 2nd Src Fx Rx 1 PAR DRV N STP 0 00Hz 00...

Страница 95: ...y If you want to set the frequency at 10Hz move the cursor to the desired place using Left Right keys Enter 10Hz using Up key and press PROG The desired frequency has been changed to 10Hz PAR DRV N STP 0 00Hz 00 Jump Code 9 CODE 01 Cmd Frequency 0 00 Hz 02 Cmd Torque 0 0 PAR DRV N STP 0 00Hz 00 Jump Code 9 CODE 01 Cmd Frequency 0 00 Hz 02 Cmd Torque 0 0 PAR DRV N STP 0 00Hz 00 Jump Code 9 CODE 01 ...

Страница 96: ...yed items for frequency the goal frequency is displayed during stop and operating frequency during operation You can set the items to display in Monitor Mode in sequence at 21 23 in CNF Move to 23 using Down key Change the 23 item in Monitor Mode to output power The third displayed item in Monitor Mode has been changed to output power MON T K N STP 0 00Hz 1 MON T K N STP 0 00Hz kW A Hz CNF N STP 0...

Страница 97: ...ine 2 2 Output Current 2 OutputCurrent 23 Monitor Line 3 3 Output Voltage 3 OutputVoltage 4 Output Power 5 WHour Counter 6 DCLink Voltage 7 DI State 8 DO State 9 V1 Monitor V 10 V1 Monitor 11 I1 Monitor mA 12 I1 Monitor 13 V2 Monitor V 14 V2 Monitor 15 I2 Monitor mA 16 I2 Monitor 17 PID Output 18 PID ref Value 19 PID Fdb Value 20 Torque 21 Torque Limit 22 Trq Bias Ref 23 Speed Limit 24 Load Speed ...

Страница 98: ...es back 2 Multiple failures at a time In case of multiple failures the number of failures is displayed next to the failure type Press PROG The type of failures is displayed Press PROG The display mode before failure checking comes back TRP current Over Voltage 01 01 Output Freq 48 30 Hz 02 Output Current 33 3 A TRP Last 1 01 Output Freq 48 30 Hz 02 Output Current 33 3 A 03 Inverter State Stop MON ...

Страница 99: ...e trip displayed If you press Reset or the terminal is entered the failure above is automatically saved and the display goes back to the place before the failure Move to Trip Mode using Mode key The most recent failure is saved in Last 1 code Press Right key A previous failure is saved in Last 2 code If another failure occurs what was in Last 2 moves to Last 3 TRP current Over Voltage 02 01 Output...

Страница 100: ...g Mode key Shift to code 40 using Down key Press PR OG Of the Parameter items to initialize select All Groups and press PROG Initialization finished you come back to the initialization selection display MON T K N STP 0 0A CNF N STP 0 0A 00 Jump Code 9 CODE 01 language Sel English 02 Inv S W Ver Version 1 00 CNF N STP 0 0A 31 Option 2 Type None 32 Option 3 Type None 40 Parameter Init No CNF N STP 0...

Страница 101: ... No Function Display Initial Setting Setting Range Unit DRV 01 Cmd Frequency 0 00 0 00 Max Frequency Hz 07 Freq Ref Src 0 KeyPad 1 0 9 You can change the frequency by changing the frequency using the keypad and pressing PROG Set DRV group 07 at KeyPad 1 The frequency changes is saved in the memory if you change the frequency at DRV group 01 and press PROG 2 Frequency Setting Using Keypad 2 KeyPad ...

Страница 102: ...16 V1 Inverting No No Yes 17 V1 Quantizing 0 04 0 04 10 Set No 06 of the input terminal block group IN at Unipolar Enter the volume resistance into the V1 terminal by using the voltage output of the external voltage output or VR output terminal of the inverter control terminal block as follows When connecting external power source When connecting internal power source 2 If you use 0 10V of the ext...

Страница 103: ...t by using the IN 07 low pass filter value but the higher the value is the responsiveness becomes slower and pulsation of a long cycle might occur The resolving power of output frequency for analog input decreases but the noise effect is reduced by the quantizing function in a system sensitive to noise The set quantization value is the percentage of the maximum analog input value Therefore if the ...

Страница 104: ...00 Set IN 06 at Bipolar Codes between 12 and 15 are displayed only when they are Bipolar and you can set the voltage between 0 and 10V which is input into the V1 terminal As follows input into the V1 terminal in volume resistance by using the voltage output of the external controller or the VR output terminal of the inv erter control terminal block When 10 10V is used from the external circuit Whe...

Страница 105: ...maximum voltage is 8V and then you set the output ratio at 80 the output frequency moves between 6Hz 48Hz For setting of 0 10V see IN 08 V1 Volt X1 IN 11 V1 Perc y2 The selection of keypad or terminal block directions and motor rotation by bipolar voltage input is shown in the following table Operating Command Voltage Input 0 10V 10 0V FWD FWD REV REV REV FWD Forward Output Frequency Input Voltage...

Страница 106: ... 40 00 and IN 23 26 is set at the default value when 20mA is input into the I1 terminal the operation is at 40 00Hz E g 2 If IN 26 is 50 and IN 01 23 26 are set at the initial value when 20mA is input into the I1 terminal the operation is at 30 00Hz IN 20 I1 Monitor displays the current input into the I1 terminal This is used for monitoring the current input at the moment IN 22 I1 Filter The set t...

Страница 107: ...00 44 V2 Volt x2 10 00 0 10 V 45 V2 Perc y2 100 00 100 0 46 V2 Inverting 0 No No Yes 47 V2 Quantizing 0 04 0 04 10 The voltage input of the extended I O inputs bipolar voltage at 10V 10V Its operating method is the same as the Bipolar input of the V1 terminal which was described on page 6 2 in detailed user s manual from website 0 20mA Input Group Code No Function Display Setting Displayed Setting...

Страница 108: ... If you mount the encoder option card on the main body of the inverter the code is displayed from APO 01 APO 01 Enc Opt Mode APO 05 Enc Pulse Sel Select No 2 Reference for APO 01 in order to set the frequency with the encoder Set APO 05 at No 2 A APO 04 Enc Type Sel APO 06 Enc Pulse Se l inputs the output method and number of pulses in harmony with the encoder specification APO 10 Enc Filter APO 1...

Страница 109: ... LS Inv 485 0 2 04 Int485 BaudR 3 9600 1200 38400 bps 07 Int485 Mode 0 D8 PN S1 0 3 1 D8 PN S2 0 3 2 D8 PE S1 0 3 3 D8 PO S1 0 3 If you set DRV 07 Freq Ref Src at Int 485 you can control the inverter through communication with the higher controller PLC or PC by using the RS485 S S terminal of the terminal block For details see Communication Functions Chapter 11 Note Please refer to User manual for...

Страница 110: ...I1 0 9 4 V2 0 9 5 I2 0 9 6 Int 485 0 9 7 Encoder 0 9 8 Fied Bus 0 9 9 PLC 0 9 IN 65 75 Px Define 21 Analog Hold 65 75 Px P1 P8 P9 P11 option This is the function of fixing the operating frequency when the terminal selected as the Analog Hold among the multi function terminals if you set the frequency by using the analog input of the control terminal block Frequency Px Operating Command Set Frequen...

Страница 111: ...vailable by using the multi function terminal Speed 0 frequency uses the frequency command selected in DRV Group No 07 Enter the desired step frequency in codes 50 64 of BAS Select the terminal to use as sequential input among multi function terminals P1 P11 and set one of the sequential functions Speed L Speed M Speed H Speed X for each Speed L Speed M Speed H and Speed X are identified as binary...

Страница 112: ...it will be checked whether another terminal block input is input for 100msec After 100msec it is accelerated or decelerated by the frequency corresponding to P6 terminal 6 1 5 Operating command setting method Group Code No Function Display Initial Display DRV 06 Cmd Source 0 Keypad 1 Fx Rx 1 2 Fx Rx 2 3 Int 485 4 Field Bus 5 PLC Select the operating command setting method in DRV Group code 06 For ...

Страница 113: ...tion of the appropriate terminal of IN 65 75 at FX and RX It stops if the FX and RX terminals are ON or OFF at the same time IN 88 Run On Delay Operation starts after the set time too when the FX or RX terminal is input It can be used where operation start synchronization with an outside sequence is necessary 3 Terminal Block operating command 2 Fx Rx 2 Group Code No Function Display Setting Displ...

Страница 114: ...Group Code No Function Display Setting Display Setting Range Unit ADV 09 Run Prevent 0 None 0 2 You can select a motor rotation direction to prevent None Both forward and reverse are available Forward Prev Forward operation is prevented Reverse Prev Reverse operation is prevented 6 1 7 Run immediately with power On Power on Run Group Code No Function Display Setting Display Setting Range Unit DRV ...

Страница 115: ... 0 600 sec Above 90kW 90 0 20 Max Freq 60 00 0 400 Hz BAS 08 Ramp T Mode 0 Max Freq Max Freq Delta Freq 09 Time scale 1 0 1 0 01 0 1 1 sec If you set BAS 08 at Max Freq you can accelerate or decelerate at an equal slope on the basis of the maximum frequency regardless of the operating frequency The acceleration time set in DRV 03 is the time it takes the frequency to reach the maximum value from 0...

Страница 116: ... Caution Be careful because change of the unit leads to change of maximum settable time If you change BAS 09 Time scale to 0 0 01sec with Acc time set at 1000 0 seconds the Acc time becomes 600 00 seconds 2 Setting of Acc Dec Time Based on Operating Frequency Group Code No Function Display Setting Display Setting Range Unit DRV 03 Acc Time 20 0 0 600 sec 04 Dec Time 30 0 0 600 sec BAS 08 Ramp T Mo...

Страница 117: ...Px Define 49 XCEL H IN 89 In Check Time 1 1 5000 msec Acc Time x Acc Time 1 3 Dec Time x Dec Time 1 3 Using the multi function terminal you can change deceleration time You can set the time of acc dec 0 in Drive Group 03 and 04 and the time of acc dec 1 3 in Drive Group 70 75 Choose the terminal for using acc dec time command between multi function terminals P1 P11 and one of the multi acc dec com...

Страница 118: ...nction Display Setting Display Setting Range Unit DRV 03 Acc Time 10 0 0 600 sec 04 Dec Time 10 0 0 600 sec BAS 70 Acc Time 1 20 0 0 600 sec 71 Dec Time 1 20 0 0 600 sec ADV 60 Xcel Change Fr 30 00 0 Max Freq Hz RPM You can Change the slop of acc dec without the use of multi function terminal Inverter operates as a slop set at BAS 70 and 71 if operating frequency is less switching frequency at ADV...

Страница 119: ...is the output voltage value of the base frequency Above the base frequency if the input voltage is higher than the set voltage the output is in proportion to the set value but if the input voltage is lower than the set voltage the input voltage is produced When 0 is set the output voltage is corrected according to the input voltage when the inverter is static Above the base frequency if the input ...

Страница 120: ... Ground Trip Latch A failure occurs when current above the prescribed amount flows due to earth in the inverter output part The earth causing current varies according to the capacity of the inverter E Thermal Latch A failure occurs in order to prevent overheat during overload operation according to the inverse time thermal characteristic Operation resumes if you set PRT 40 at values other than 0 O...

Страница 121: ...al Of the IN65 75 functions No 3 External Trip is selected BX Level The inverter output is blocked by function selection of the multi function terminal Of the IN65 75 functions No 4 BX is selected H W Diag Fatal Trouble with the memory device within the inverter EPP ROM analog digital switch output ADC Off Set or CPU malfunction Watch Dog 1 Watch Dog 2 EEP Err In the event of problems during Param...

Страница 122: ...set in PRT 70 Dev Speed Trip Latch A failure occurs when the speed that got feedback from the encoder goes up above the set variation value Operation resumes if PRT 73 is set at 1 Encoder Trip Latch A failure occurs when PRT 77 Enc Wire Check is set at 1 and abnormality is detected for the set period of time Pre PID Fail Latch A failure occurs when the control amount PID feedback is continuously i...

Страница 123: ...Trip 3 Latch When the option gets out of the option slot No 3 after it was inserted during power supply or when communication is not available with the inverter I O Board Trip Latch When the basic and insulated I O boards are disconnected or have a fault of connection Note Level automatically terminates when the failure is solved This is not saved in the failure history Latch terminates when the r...

Страница 124: ...the prescribed degree The detection level is set at PRT 66 Enc Conn Check An alarm is signified if No 3 Enc Test is selected from BAS 20 Auto Tuning and no signal is input during the encoder test Signals are released if ENC Tune is set among the functions of OUT31 33 Enc Dir Check An alarm is signified if No 3 Enc Test is selected from BAS 20 Auto Tuning and the setting is wrongly changed between ...

Страница 125: ...60 Check the machine brake Over Voltage Decelerating time is too short compared with the inertia of the load GD2 Regenerative load is located at the inverter output The supply voltage is too high Set the decelerating time higher Use a braking resistance device Check whether the supply voltage is above the prescribed degree Low Voltage Low Volatage2 The supply voltage is too low Load larger than th...

Страница 126: ...educe the torque boost amount Over Heat There is a problem with the cooling system The inverter has been used longer than the replacement cycle of the cooling fan The surrounding temperature is too high Check whether there is any foreign substance in the vent air duct or outlet Replace the inverter cooling fan Keep the temperature around the inverter below 50 C Over Current2 Earth of the output co...

Страница 127: ...an become to change period time Internal fan PCB board s power connector is connected Inverter cooling fan have to changed No Motor Trip The motor is disconnected to the output of inverter The current level of detection of Trip is incorrect Check the connection of wiring Check the value of parameter both BAS 13 Rated current and PRT 32 No Motor Level ...

Страница 128: ...cket on the bottom to the arrow direction and pull it forward Disconnect the connector of the fan then you can replace the fan below 3 7kW below 7 5 kW 2 Replacement steps of product of 11 15kW 200V 400V 18 5 22 kW 400V Release the volts under the In Out put terminals and disconnect the connector of the fan then you can replace the fan ...

Страница 129: ...ng and Troubleshooting 7 10 3 Replacement steps of product of 18 5 22 kW 200V 30 75kW 200V 400V Check capacity Release the volts upper of the product and disconnect the connector of the fan then you can replace the fan ...

Страница 130: ... digital volt meter may result in spurious operation or indicate wrong value due to high frequency PWM output voltage of the inverter If the inverter has not been operated for a long time capacitors lose their charging characteristics and are depleted To prevent depletion turn on the product once a year and allow the device to operate for 30 60 min Run the device under no load conditions 1 Checkin...

Страница 131: ...d be 10 40 degree C Freezing is not allowed Ambient humidity to be 50 or less Dew is not allowed Temperature meter Humidity meter Recorder Entire system Isn t there any vibration or unusual sound Judgement by visual or auditory sense There must be no unusual record Power Voltage Is the main circuit voltage normal Check the voltage among R S and T phases on the inverter terminal block Digital Multi...

Страница 132: ...record Temperature meter Indicator Meter Is the indicator value normal Check the indicator value on the display of the panel surface Check the value under the regulation and standard value Volt Meter Current Meter etc Motor Entire system 1 Isn t there any unusual vibration or unusual sound 2 Isn t there any unusual smell 1 Check by ear hand and eye 2 Check overheat damage etc 3 Check the area conn...

Страница 133: ...ny corrosion on the conductor 2 Isn t there any damage to the wire sheath 1 Switch the power Off and then turn it with a hand 2 Fasten it once again 1 Rotate it softly 2 There must be no unusual record Terminal block Isn t it damaged Check by eyes There must be no unusual record Flat condenser Measure the electrostatic capacity Measure using the capacity meter 85 or more of the rated capacity Capa...

Страница 134: ... part that cannot be replaced replace the inverter itself Control circuit protecting circuit Operation 1 Check the unbalance of the output voltage during the operation of inverter 2 Display circuit must not have any unusual phenomenon after the sequence protecting operation test is done 1 Measure the voltage among the U V and W at the Inverter output terminal 2 Have the inverter protecting circuit...

Страница 135: ...al and the ground terminal Unfasten the connection of the inverter and then measure the gap among R S T U V and W terminals and this area after having them shorted out 5MΩ or more DC 500V Class Megger Motor Resistance Insulation Megger checking between the output terminal and the ground terminal Unfasten the connection among U V and W and then bind the motor wiring 5MΩ or more 500V Class Megger Ca...

Страница 136: ...104 DecTime decelerating time 0 600 s Below75kW 30 0 O O O O O O Above90kW 90 0 06 0h1106 Cmd Source operating command method 0 Keypad 1 Fx Rx 1 X O O O O O 1 Fx Rx 1 2 Fx Rx 2 3 Int485 4 FieldBus 5 PLC 07 0h1107 Freq Ref Src frequency setting method 0 Keypad 1 0 Keypad 1 X O O O X X 08 0h1108 Trq Ref Src torque command method 0 Keypad 1 0 Keypad 1 X X X X O O 1 Keypad 2 2 V1 3 I1 4 V2 5 I2 6 Int4...

Страница 137: ...19 132kW 21 185kW 23 280kW 25 375kW depends on inverter capacity X O O O O O 15 0h110F Torque Boost torque boost method 0 Manual 0 Manual X O X X X X 1 Auto 16 Note2 0h1110 Fwd Boost forward torque boost 0 15 Below75kW 2 0 X O X X X X Above90kW 1 0 17 0h1111 Rev Boost reverse torque boost Below75kW 2 0 X O X X X X Above90kW 1 0 18 0h1112 Base Freq base frequency 30 400 Hz 60 00 X O O O O O 19 0h11...

Страница 138: ...ement selection 0 M G A 0 M G A X O O O X X 1 M G A 2 M G A 3 M M 2 G A 4 M G 2 A 50 5 M G 2 A 50 6 M G 2 A 50 7 M M G 2 A 50 03 0h1203 Aux Ref Gain auxiliary command gain 200 0 200 0 100 0 O O O O X X 04 0h1204 Cmd 2nd Src 2nd operation command method 0 Keypad 1 Fx Rx 1 X O O O O O 1 Fx Rx 1 2 Fx Rx 2 3 Int485 4 FieldBus 5 PLC 05 0h1205 Freq 2nd Src 2nd frequency Setting method 0 Keypad 1 0 Keypa...

Страница 139: ...el input power frequency 0 60Hz 0 60Hz X O O O O O 1 50Hz 11 0h120B Pole Number motor pole 2 48 Itdependson invertercapacity X O O O O O 12 0h120C Rated Slip rated sleep speed 0 3000 rpm X O O O O O 13 0h120D Rated Curr motor rated current 1 1000 A X O O O O O 14 0h120E Noload Curr motor no load current 0 5 1000 A X O O O O O 15 0h120F Rated Volt motor rated voltage 180 480 V 0 X O O O O O 16 0h12...

Страница 140: ...50 Note6 0h1232 Step Freq 1 step frequency 1 Start freq max freq Hz 10 00 O O O O X X 51 0h1233 Step Freq 2 2 20 00 O O O O X X 52 0h1234 Step Freq 3 3 30 00 O O O O X X 53 0h1235 Step Freq 4 4 40 00 O O O O X X 54 0h1236 Step Freq 5 5 50 00 O O O O X X 55 0h1237 Step Freq 6 6 60 00 O O O O X X 56 0h1238 Step Freq 7 7 60 00 O O O O X X 57 0h1239 Step Freq 8 8 55 00 O O O O X X 58 0h123A Step Freq ...

Страница 141: ... X X 82 0h1252 Acc Time 7 Acc Dec Time 7 0 600 sec 80 0 O X X 83 0h1253 Dec Time 7 Acc Dec Time 7 0 600 sec 80 0 O X X The grey code refers to hidden code emerging only in case of setting of the code Note 4 BAS 24 is shown only when DRV 09 Control Mode is set as Sensorless 2 or Vector Note 5 BAS 41 48 is displayed only when it is set as User V F even if there is only one BAS 07 or M2 V F Patt M2 2...

Страница 142: ...3 Reserved 4 Powr Braking 09 0h1309 Run Prevent rotationpreventing directionselection 0 None 0 None X O O O X X 1 Forward Prev 2 Reverse Prev 10 0h130A Power on Run powerinputstarting 0 No 0 No O O O O X X 1 Yes 12 Note8 0h130C Dc StartTime startingDCbrakingtime 0 60 s 0 00 X O O O X X 13 0h130D Dc Inj Level DCsupply 0 200 50 X O O O X X 14 Note9 0h130E Dc BlockTime Pre DCbrakingoutput blocktime 0...

Страница 143: ... Rls Curr brakeopencurrent 0 180 0 50 0 O O O O X X 42 0h132A BR Rls Dly brakeopendelaytime 0 10 00 s 1 00 X O O O X X 44 0h132C BR Rls Fwd Fr brakeopen forwardfrequency 0 400 Hz 1 00 X O O O X X 45 0h132D BR Rls Rev Fr brakeopen reversefrequency 1 00 X O O O X X 46 0h132E BR Eng Dly brakeclosedelaytime 0 10 s 1 00 X O O O X X 47 0h132F BR Eng Fr brakeclosefrequency 0 400 Hz 2 00 X O O O X X 50 0h...

Страница 144: ... Off Ctrl Src 0 None 0 None X O O O O O 1 V1 2 I1 3 V2 4 I2 67 0h1343 On C Level Output contact point ON level 10 100 90 00 X O O O O O 68 0h1344 Off C Level Output contact point OFF level 100 00 outputcontact pointONlevel 10 00 X O O O O O 70 0h1346 Run En Mode safety operation selection 0 AlwaysEnable 0 Always Enable X O O O O O 1 DIDependent 71 Note14 0h1347 Run Dis Stop safety operation stop m...

Страница 145: ...BUnitOperatingVoltage 200V 350 400 V 390 V X O O O O O 400V 600 800 V 780 V 80 0h1350 FireModeSel FireFunctionSelect 0 None 0 None X O O O X X 1 FireMode 2 FireTest 81주16 0h1351 FireModeFreq FireModeFrequency 0 MaxFreq Hz 60 00 X O O O X X 82 0h1352 FireqModeDir Fire Mode Operating Direction 0 Forward 0 Forward X O O O X X 1 Reverse 83 FireModeCnt FireModeCounter 0 99 0 X O O O X X The grey code r...

Страница 146: ...140A Flux Force Initial flux power supply 100 500 100 0 X X X O O O 11 0h140B HoldTime permanent operation sustaining time 0 60 s Depends on controlmode X X X O X X 12 0h140C ASR P Gain 1 speed control period proportional gain1 10 500 50 0 O X X O X X 13 0h140D ASR I Gain 1 speed control period integral calculus gain 1 10 9999 ms 300 O X X O X X 15 0h140F ASR P Gain 2 speed control period Proporti...

Страница 147: ... X 27 0h141B Observer Gain2 Sensorless 2 measurer gain 2 1 1000 100 0 O X X X X X 28 0h141C Observer Gain3 Sensorless 2 measurer gain 3 0 30000 13000 O X X X X X 29 0h141D S Est P Gain1 Sensorless 2 speed estimator proportional gain 1 0 30000 Depends on motor capacity O X X X X X 30 0h141E S EstIGain1 Sensorless2speed estimatorintegral calculusgain1 O X X X X X 31 0h141F S Est P Gain2 Sensorless2 ...

Страница 148: ... 5 I2 6 Int 485 7 Encoder 8 FiedBus 9 PLC 10 Synchro 11 BinaryType 54 Note18 0h1436 FWD Trq Lmt forward offsetting Torque limit 0 200 180 0 O X X X O O 55 0h1437 FWD Trq Lmt forward regenerative torque limit O X X X O O 56 0h1438 REV Trq Lmt reverse offsetting torque limit O X X X O O 57 0h1439 REV Trq Lmt reverse regenerative torque limit O X X X O O The grey code refers to hidden code emerging o...

Страница 149: ... limit setting method 0 Keypad 1 0 Keypa d 1 O X X X X O 1 Keypad 2 2 V1 3 I1 4 V2 5 I2 6 Int 485 7 FiedBus 8 PLC 63 0h143F FWDSpeed Lmt forward speed limit 0 max freq Hz 60 00 O X X X X O 64 0h1440 REVSpeed Lmt reverse speed limit O X X X X O 65 0h1441 Speed Lmt Gain Speed limit operation gain 100 5000 500 O X X X X O 66 0h1442 Droop Perc droop operation amount 0 100 0 0 O X X X X O 67 Note19 0h1...

Страница 150: ...1448 SS Sup Current speed search standard current 80 200 Below 75kW 150 O O O X X X Above 90kW 100 73 0h1449 SS P Gain speed search proportional gain 0 9999 100 O O O X X X 74 0h144A SS I Gain speed search integral calculus gain 0 9999 200 O O O X X X 75 0h144B SS BlockTime Pre speed search output block time 0 60 s 1 0 X O O X X X 77 0h144D KEBSelect energybufferingselection 0 None 0 None X O O O ...

Страница 151: ...elcting the Current anti hunting 0 No 0 No X X X X 1 Yes 91 0h145B AHRP Gain Current Anti hunting FunctionProtection 0 32767 1000 X X X X X The grey code refers to hidden code emerging only in case of setting of the code Note 20 CON 72 75 are displayed only when CON 71 77 KEB Select is set as bit or other than None Note 21 CON 82 83 are displayed only when DRV 09 Control Mode is set as Vector Note...

Страница 152: ...100 00 O O O O O O 12 Note 22 0h150C V1 Voltx1 V1 inputminimumvoltage 10 0 V 0 00 O O O O O O 13 0h150D V1 Percy1 V1 minimumvoltageoutput 100 0 0 00 O O O O O O 14 0h150E V1 Voltx2 V1 inputmaximumvoltage 10 0 V 10 00 O O O O O O 15 0h150F V1 Percy2 V1 maximumvoltageoutput 100 0 100 00 O O O O O O 16 0h1510 V1Inverting rotationdirectionchange 0 No 0 No O O O O O O 1 Yes 17 0h1511 V1Quantizing V1qua...

Страница 153: ...C V2 Volt x2 V2 inputmaximumvoltage 10 0 V 10 00 O O O O O O 45 0h152D V2 Perc y2 output atV2 maximumvoltage 100 0 100 00 O O O O O O 46 0h152E V2 Inverting rotationdirectionchange 0 No 0 No O O O O O O 1 Yes 47 0h152F V2 Quantizing V2quantizationlevel 0 04 10 0 04 O O O O O O 50 0h1532 I2 Monitor mA I2inputamountdisplay 0 20 mA 0 00 O O O O O O 52 0h1534 I2 Filter I2inputfiltertimeconstant 0 1000...

Страница 154: ...7 P7 Define P7 7 Speed L 9 Sp H X O O O O O 72 0h1548 P8 Define P8 8 Speed M 6 JOG X O O O O O 73 Note24 0h1549 P9 Define P9 9 Speed H 0 NONE X O O O O O 74 0h154A P10 Define P10 10 Speed X X O O O O O 75 0h154B P11 Define P11 11 XCEL L X 12 XCEL M 13 RUN Enable 14 3 Wire 15 2nd Source 16 Exchange 17 Up 18 Down 19 U D Save 20 U D Clear 21 Analog Hold 22 I Term Clear 23 PID Openloop 24 PGain2 25 XC...

Страница 155: ...ct 51 FireMode 85 0h1555 DI On Delay multi functioninput terminalONfilter 0 10000 ms 10 O O O O O O 86 0h1556 DI Off Delay multi functioninput terminalOFFfilter 3 O O O O O O 87 0h1557 DINC NO Sel multi functioninput contactpointselection P8 P1 00000000 X O O O O O 0 Acontactpoint NO 1 Bcontactpoint NC 88 0h1558 RunOn Delay operatingcommand delaytime 0 100 s 0 00 X O O O O O 89 0h1559 InCheck Time...

Страница 156: ...ev 12 PIDRefValue 13 PIDFbkValue 14 PIDOutput 15 Constant 02 0h1602 AO1 Gain analog output1 gain 1000 1000 100 0 O O O O O O 03 0h1603 AO1 Bias analog output 1 bias 100 100 0 0 O O O O O O 04 0h1604 AO1 Filter analog output1 filter 0 10000 ms 5 O O O O O O 05 0h1605 AO1 Const analog constant output 1 0 100 0 0 O O O O O O 06 0h1606 AO1 Monitor analog output 1 monitor 0 1000 0 0 O O O O O 07 0h1607...

Страница 157: ... O O O O O O 1 Current 2 Voltage 3 DCLinkVolt 4 Torque 5 Watt 6 Idse 7 Iqse 8 TargetFreq 9 RampFreq 10 SpeedFdb 11 SpeedDev 12 PIDRefValue 13 PIDFbkValue 14 PIDOutput 15 Constant 15 0h160F AO3 Gain analogoutput3gain 1000 1000 100 0 O O O O O O 16 0h1610 AO3 Bias analogoutput3bias 100 100 0 0 O O O O O O 17 0h1611 AO3 Filter analogoutput3filter 0 10000 ms 5 O O O O O O 18 AO3Const analogconstantout...

Страница 158: ...onrelay1item 0 NONE 29 Trip O O O O O O 32 0h1620 Relay 2 multi functionrelay2item 1 FDT 1 14 Run O O O O O O 33 0h1621 Q1 Define multi functionoutput1item 2 FDT 2 1 FDT 1 O O O O O O 34 Note26 0h1622 Relay 3 multi functionoutput3item 3 FDT 3 2 FDT 2 O O O O O O 35 0h1623 Relay 4 multi functionoutput4item 4 FDT 4 3 FDT 3 O O O O O O 36 0h1624 Relay 5 multi functionoutput5item 5 OverLoad 4 FDT 4 O ...

Страница 159: ...ctionoutputcontactpoint selection Q1 Relay2 Relay1 000 X O O O O O 0 Acontactpoint NO 1 Bcontactpoint NC 53 0h1635 TripOut OnDly failureoutputONdelay 0 100 s 0 00 O O O O O O 54 0h1636 TripOut OffDly failureoutputOFFdelay 0 100 00 s 0 00 O O O O O O 55 0h1637 TimerOn Delay timerONdelay 0 00 O O O O O O 56 0h1638 TimerOff Delay timerOFFdelay 0 00 O O O O O O 57 0h1639 FDT Frequency detectionfrequen...

Страница 160: ...fter reception 0 1000 ms 5ms O O O O O O 06 Note27 0h1706 FBus S W Ver communicationoptionS W version 1 00 O O O O O O 07 0h1707 FBus ID communicationoption inverterID 0 255 1 O O O O O O 08 0h1708 FBUS BaudRate FBuscommunication speed 12Mbps O O O O O 09 0h1709 FieldBus LED communicationoptionLED status O O O O O O 30 0h171E ParaStatusNum 0 8 3 O O O O O O 31 0h171F ParaStauts 1 output address 1 ...

Страница 161: ...h1747 Virtual DI 2 2 1 FX O O O O O O 72 0h1748 Virtual DI 3 3 2 RX O O O O O O 73 0h1749 Virtual DI 4 4 3 RST O O O O O O 74 0h174A Virtual DI 5 5 4 ExternalTrip O O O O O O 75 0h174B Virtual DI 6 6 5 BX O O O O O O 76 0h174C Virtual DI 7 7 6 JOG O O O O O O 77 0h174D Virtual DI 8 8 7 Speed L O O O O O O 78 0h174E Virtual DI 9 9 8 Speed M O O O O O O 79 0h174F Virtual DI 10 10 9 Speed H O O O O O...

Страница 162: ...p 46 FWD JOG 47 REV JOG 48 Trq Bias 49 XCEL H 50 KEB Select 51 Fire Mode 86 0h1756 Virt DI Status Comm Multi function inputmonitoring 0 X O O O O O 90 0h175A Comm Mon Sel monitortypeselection 0 Int 485 0 Int485 O O O O O O 1 Keypad 91 0h175B RcvFrame Num Numberofreception frames 0 O O O O O 92 0h175C Err Frame Num Numberoferrorframes 0 O O O O O 93 0h175D Nak Frame Num Numberofwritingerror frames ...

Страница 163: ... TrvOffsetHi traverseoffsetupperlimit 0 20 0 0 0 O O O O X X 13 0h180D TrvOffsetlo traverseoffsetlowerlimit 0 0 O O O O X X 16 Note29 0h1810 PIDOutput PIDoutputmonitor 0 00 O O O X X 17 0h1811 PIDRefValue PIDreferencemonitor 50 00 O O O X X 18 0h1812 PIDFdbValue PIDfeedbackmonitor 0 00 O O O X X 19 0h1813 PIDRefSet PIDreferencesetting 100 100 50 O O O O X X 20 0h1814 PID Ref Source PIDreferencesel...

Страница 164: ...cess PID 0 Proc ess PID X O O O X X 1 Normal PID 29 0h181D PID Limit Hi PIDupperlimitfrequency PID lower limit frequency Hz 300 Hz 60 00 O O O O X X 30 0h181E PID Limit Lo PIDlowerlimitfrequency 300 PID upper limit frequency Hz 60 00 O O O O X X 31 0h181F PID Out Inv PIDoutputreversal 0 No 0 No X O O O X X 1 Yes 32 0h1820 PID Out Scale PIDoutputscale 0 1 1000 100 0 X O O O X X 34 0h1822 Pre PID Fr...

Страница 165: ...9 kW 1 0 HP 11 1 2 43 0h182B PID Unit Gain PIDunitgain 0 300 100 00 O O O O X X 44 0h182C PID Unit Scale PIDunitscale 0 X 100 2 x1 O O O O X X 1 X 10 2 X 1 3 X 0 1 4 X 0 01 45 0h182D PID P2 Gain PID2nd proportionalgain 0 1000 100 0 X O O O X X The grey code refers to hidden code emerging only in case of setting of the code Note 29 APP 16 45 codes are displayed only whenAPP 01 App Mode is set as Pr...

Страница 166: ...C Seq1 1 SteadT 1 1steadyspeedoperationtime O O O O X X 13 0h190D Seq1 1Dir 1 1operationdirection 0 Reverse 1 Forward O O O O X X 1 Forward 14 0h190E Seq1 2 Freq 1 2stepfrequency 0 01 maximum frequency Hz 21 00 O O O O X X 15 0h190F Seq1 2 XcelT 1 2Acc Dectime 0 1 600 0 s 5 0 O O O O X X 16 0h1910 Seq1 2 SteadT 1 2steadyspeedoperationtime O O O O X X 17 0h1911 Seq1 2Dir 1 2operationdirection 0 Rev...

Страница 167: ...operationdirection 0 Reverse 1 Forward 8 59 O O O X X 1 Forward 34 0h1922 Seq1 7 Freq 1 7stepfrequency 0 01 maximum frequency Hz 51 00 O O O O X X 35 0h1923 Seq1 7 XcelT 1 7Acc Dectime 0 1 600 0 s 5 0 O O O O X X 36 0h1924 Seq1 7 SteadT 1 7steadyspeedoperationtime O O O O X X 37 0h1925 Seq1 7Dir 1 7operationdirection 0 Reverse 1 Forward O O O O X X 1 Forward 38 0h1926 Seq1 8 Freq 1 8stepfrequency ...

Страница 168: ...req 2 4stepfrequency 0 01 maximum frequency Hz 42 00 O O O O X X 56 0h1938 Seq2 4 XcelT 2 4Acc Dectime 0 1 600 0 s 5 0 O O O O X X 57 0h1939 Seq2 4 SteadT 2 4steadyspeedoperationtime O O O O X X 58 0h193A Seq2 4Dir 2 4operationdirection 0 Reverse 1 Forward O O O O X X 1 Forward 59 0h193B Seq2 5 Freq 2 5stepfrequency 0 01 maximum frequency Hz 52 00 O O O O X X 60 0h193C Seq2 5 XcelT 2 5Acc Dectime ...

Страница 169: ...celT 2 8Acc Dectime 0 1 600 0 s 5 0 O O O O X X 73 0h1949 Seq2 8 SteadT 2 8steadyspeedoperationtime O O O O X X 74 0h194A Seq2 8Dir 2 8operationdirection 0 Reverse 1 Forward O O O O X X 1 Forward The grey code refers to hidden code emerging only in case of setting of the code Note 30 AUT group is displayed only whenAPP 0 1 App Mode is set as Auto Sequence Note 31 AUT 04 codes are displayed only wh...

Страница 170: ...0h1A0E EncPercy2 Encmaximumpulse시 output 0 100 100 O O X O X O 20 Note36 0h1A14 AuxMotorRun displayofnumberofauxiliarymotor movement 0 4 0 O O O O X X 21 0h1A15 StartingAux startingauxiliarymotorselection 1 4 1 X O O O X X 22 0h1A16 AutoOpTime autochangeoperationtime XX XX Min 0 00 O O O O X X 23 0h1A17 StartFreq1 1stauxiliarymotorStartfrequency 0 60 Hz 49 99 O O O O X X 24 0h1A18 StartFreq2 2ndau...

Страница 171: ...O O O O 61 0h1A3D PLCWrData2 PLCwritedata2 O O O O O O 62 0h1A3E PLCWrData3 PLCwritedata3 O O O O O O 63 0h1A3F PLCWrData4 PLCwritedata4 O O O O O O 64 0h1A40 PLCWrData5 PLCwritedata5 O O O O O O 65 0h1A41 PLCWrData6 PLCwritedata6 O O O O O O 66 0h1A42 PLCWrData7 PLCwritedata7 O O O O O O 67 0h1A43 PLCWrData8 PLCwritedata8 O O O O O O 76 0h1A4C PLCRdData1 PLCreaddata1 O O O O O O 77 0h1A4D PLCRdDa...

Страница 172: ...ovementincaseofKeypad commandloss 0 None 0 None O O O O O O 1 Warning 2 Free Run 3 Dec 12 0h1B0C LostCmdMode movementincaseofspeed commandloss 0 None 0 None O O O O O O 1 Free Run 2 Dec 3 Hold Input 4 Hold Output 5 Lost Preset 13 Note39 0h1B0D LostCmdTime Speedcommandlossjudgment time 0 1 120 s 1 0 O O O O O O 14 0h1B0E LostPresetF operationfrequencyincaseof speedcommandloss Startfreq maximumfrequ...

Страница 173: ...el movementselectionaftermotor overheatdetectionsensor detection 0 None 0 None O O O O O O 1 Free Run 2 Dec 35 0h1B23 ThermalIn Src motoroverheat detectionsensor inputselection 0 None 0 None X O O O O O 1 V1 2 I1 3 V2 4 I2 36 0h1B24 Thermal TLev motoroverheatdetection sensorfailurelevel 0 100 50 0 O 37 0h1B25 Thermal TArea motoroverheatdetection sensorfailurearea 0 Low 0 Low O O O O O O 1 High 40 ...

Страница 174: ...1B48 OverSPD Time overspeedjudgmenttime 0 01 10 00 s 0 01 O X X O X O 73 0h1B49 SpeedDev Trip speederrorfailure 0 No 0 No O X X O X X 1 Yes 74 0h1B4A SpeedDev Band speederrorwidth 2 max freq Hz 20 00 O X X O X X 75 0h1B4B SpeedDev Time speed errorjudgment time 0 1 1000 0 s 1 0 O X X O X X 77 0h1B4D EncWire Check Encoderoption connectioncheck 0 No 0 No O X X O X O 1 Yes 78 0h1B4E EncCheck Time Enco...

Страница 175: ...ornoloadcurrent 0 5 1000 0 A X O O X O X 14 0h1C0E M2 RatedVolt motorratedvoltage 180 480 V X O O X O X 15 0h1C0F M2 Efficiency motorefficiency 70 100 X O O X O X 16 0h1C10 M2 InertiaRt loadinertiaratio 0 8 X 17 M2 Rs statorresistance 0 999 9 X 18 M2 Lsigma leakinductance 0 9 999 mH X 19 M2 Ls statorinductance 0 99 99 mH X O O X O X 20 M2 Tr rotortimeconstant 25 5000 ms X O O X O X 25 0h1C19 M2 V ...

Страница 176: ...00 00 00 00 10 Trip Delete deletion of failure history 0 No 0 No 1 Yes 8 1 14 Config Mode CNF No FunctionDisplay Name SettingRange InitialValue 00 Jump Code jump code 0 99 1 01 Language Sel keypad language selection 0 English 0 English 1 Russian 2 Español 3 Polski 4 Turkish 02 LCD Contrast LCD brightness adjustment 10 Inv S W Ver body S W version 1 XX 11 KeypadS W Ver keypad S W version 1 XX 12 KP...

Страница 177: ...it monitor mode initialization 0 No 0 No 1 Yes 30 Option 1Type option slot 1 type display 0 None 0 None 31 Option 2Type option slot 2 type display 1 PLC 0 None 32 Option 3Type option slot 3 type display 2 Profi 0 None 3 Ext I O 4 Encoder 40 Parameter Init parameter initialization 0 No 1 AllGrp 2 DRVGrp 3 BASGrp 4 ADVGrp 5 CONGrp 6 INGrp 7 OUTGrp 8 COMGrp 9 APPGrp 10 AUTGrp 11 APOGrp 12 PRTGrp 13 M...

Страница 178: ...Un locked 51 View Lock Pw parameter mode hiding password Password 52 Key Lock Set parameter editing lock Un locked 53 Key Lock Pw parameter editing lock Password 60 AddTitle Del Keypad title version up 0 No 0 No 1 Yes 61 Easy Start On Easy parameter setting 0 No 1 Yes 1 Yes 62 WHCount Reset consumed power amount initialization 0 No 0 No 1 Yes 70 On time inverter movement cumulative time mm dd yy h...

Страница 179: ... y2 Output at V1 maximum voltage 0 100 100 00 15 V1 Volt x1 V1 input minimum voltage 10 0 V 0 00 16 V1 Perc y1 output at V1 minimum voltage 100 0 0 00 17 V1 Volt x2 V1 input maximum voltage 10 0 V 10 00 18 V1 Perc y2 output at V1 maximum voltage 100 0 100 00 19 V1 Inverting rotation direction change 0 1 0 No 20 I1 Monitor mA I1 input amount display 0 20 mA 0 00 21 I1 Polarity I1 polarity display 0...

Страница 180: ... 9 0 Keypad 1 05 Control Mode control mode 0 5 0 V F 06 TrvApmlit traverse operating range 0 20 0 0 07 Trv Scramb traverse scramble magnitude 0 50 0 0 08 TrvAccTime traverse accelerating time 0 1 600 s 2 0 09 Trv DecTime traverse decelerating time 3 0 10 Trv Offset Hi traverse offset upper limit 0 20 0 0 11 Trv Offset lo traverse offset lower limit 0 0 12 P1 Define P1terminal function setting 0 48...

Страница 181: ...Chapter 8 Table of Functions 8 46 ...

Страница 182: ...nverter Electric contactor Possible to Select This does not have to be necessarily installed but if you do do not start or stop the inverter frequently with the contactor It might decrease the life of the inverter AC and DC reactor Possible to Select The reactor is necessary for installation where power factor improvement or input power capacity is high over 1000kVA distribution distance below 10m...

Страница 183: ...S603c 630 MC 630a 630 0008iS7 4 ABS33c 15 UTE100 15 EBS33c 15 MC 9b 9 0015iS7 4 ABS33c 15 UTE100 15 EBS33c 15 MC 9b 9 0022iS7 4 ABS33c 15 UTE100 15 EBS33c 15 MC 12b 12 0037iS7 4 ABS33c 15 UTE100 15 EBS33c 15 MC 18b 18 0055iS7 4 ABS33c 30 UTE100 30 EBS33c 30 MC 22b 22 0075iS7 4 ABS33c 30 UTE100 30 EBS33c 30 MC 32a 32 0110iS7 4 ABS53c 50 UTS150 50 EBS53c 50 MC 40a 40 0150iS7 4 ABS63c 60 UTS150 60 EB...

Страница 184: ...mal Duty load factor In operation Heavy Duty Improvement may be lower than the displayed in 1 Caution English Use Class H or RK5 UL listed Input fuses and UL listed breakers ONLY See the table above for the voltage and current ratings for the fuses and breakers French Utiliser UNIQUEMENT des fusibles d entrée homologués de Classe H ou RK5 UL et des disjoncteurs UL Se reporter au tableau ci dessus ...

Страница 185: ... 30 0037iS7 4 2 34 10 1 22 15 0055iS7 2 0 39 30 0 28 40 0055iS7 4 1 22 15 1 14 20 0075iS7 2 0 28 40 0 20 59 0075iS7 4 1 14 20 0 81 30 0110iS7 2 0 20 59 0 15 75 0110iS7 4 0 81 30 0 61 38 0150iS7 2 0 15 75 0 12 96 0150iS7 4 0 61 38 0 45 50 0185iS7 2 0 12 96 0 10 112 0185iS7 4 0 45 50 0 39 58 0220iS7 2 0 10 112 0 07 160 0220iS7 4 0 39 58 0 287 80 0300iS7 2 0 07 160 0 05 200 0300iS7 4 0 287 80 0 232 9...

Страница 186: ... 185 220kW SV2200DB 4 주1 Refer to the appearance of Group 4 280 375Kw SV2200DB 4 2Set Type C Resistanc e of DB Resistor refer to the manual of DB Unit 200V 30 37 kW LSLV0370DBU 2LN Group 5 LSLV0370DBU 2HN Group 6 45 55 kW 75 kW LSLV0750DBU 2LN Group 5 LSLV0750DBU 2HN Group 6 400V 30 37 kW LSLV0370DBU 4LN Group 5 LSLV0370DBU 4HN Group 6 45 55 kW 75kW LSLV0750DBU 4LN Group 5 90 kW LSLV0900DBU 4HN Gr...

Страница 187: ...minal for connection with N of Inverter P Terminal for connection with P1 of Inverter Note READ DBU User manual certainly when selecting DB resistors Group 3 Group 4 Terminals Functions G Ground Terminal B2 Terminal for connection with B2 of DBU B1 Terminal for connection with B1 of DBU N Terminal for connection with N of Inverter P Terminal for connection with P of Inverter N B2 P B1 G B1 N P G B...

Страница 188: ...und Terminal Group 6 AFrame B Frame C Frame 37kW 75kW 4 75kW 2 90 220kW Terminals Functions P Terminal for connection with P of Inverter N Terminal for connection with N of Inverter B1 Terminal for connection with B1 of DBU B2 Terminal for connection with B2 of DBU N C Unused E Ground Terminal Note You must refer to dynamic braking unit manual for choice the braking resistor to use the dynamic bra...

Страница 189: ...ns Group 1 Group 2 DBU Terminals Description B1 B2 Wire correctly referring to wiring diagram DB Resistors connect with B1 B2 of DB Unit 5 5 258 5 245 2 Ø 5 5 80 80 123 Dynamic Braking Unit RESET POWER RUN OHT OCT 231 5 12 15 27 130 75 InputPower DynamicBraking Resistor DynamicBraking Unit Motor IM ynamic R T S U N P P2 W V D B1 N P G WIRING B2 B2 B1 U raking B nit 166 2 ...

Страница 190: ... 제 용 P G N B2 R2 R1 R S T IM W V U N WIRING P P2 B1 P G N B2 R2 R1 R S T IM W V U N WIRING P P2 B1 적 품 제 용 Group 5 Voltage Capacity of applied motor Dimension mm Hole position for installation Weight Hole size for installation V kW W H H2 D W1 H1 kg φ 220 15 140 227 4 192 76 4 125 215 4 1 50 M4 22 1 55 37 1 57 75 1 84 440 15 1 53 22 1 55 37 1 56 75 1 85 ...

Страница 191: ...position for installation Weight Hole size for installation V kW W H H2 D W1 H1 kg φ AFrame 220 37 50 200 219 190 165 2 160 208 5 3 77 M6 440 37 50 3 84 75 50 3 98 B Frame 220 75 50 215 340 311 175 329 5 8 26 90 50 8 48 440 90 50 8 30 132 50 8 40 C Frame 440 160 50 240 380 351 200 369 5 9 40 220 50 9 70 ...

Страница 192: ...er Heat Trip OHT Displays Function description POWER Red LED POWER LED is turned On when main power is supplied Generally POWER LED is turn On while main power supplied because DBU is connected with inverter RUN Green LED RUN LED is turned off while DBU is ON by regenerative energy of Motor OHT Green LED Under Breaking if the temperature is exceeded over setting value due to over heat of Heatsink ...

Страница 193: ...0 10 2400 TYPE 3 13 3 15 MCRM2400W8 8 2400 TYPE 3 13 3 18 5 MCRM3600W5 5 3600 TYPE 3 13 3 22 MCRM3600W5 5 3600 TYPE 3 13 3 30 5 5000 100 braking torque 10 ED 37 SV370DBU 2U 4 5 7000 45 3 5 10000 55 SV550DBU 2U 3 0 15000 75 2 5 20000 4 0 0 V C l a s s 0 75 600 150 TYPE 1 150 braking torque 5 ED 1 25 1 5 300 300 TYPE 1 2 2 2 MCRB400W200 200 400 TYPE 1 2 3 7 MCRB600W130 130 600 TYPE 2 2 5 5 MCRM1000W...

Страница 194: ...esistance value in the table above 2 If the braking resistor type name is not listed in the table above purchase separately a braking resistor reference to resistance and wattage in the table above 2 Appearance and size of braking resistor TYPE Size mm W H D A B C 1 64 410 30 392 6 2 128 390 43 65 373 6 3 220 345 93 140 330 7 8 4 220 445 93 140 428 7 8 5 220 445 165 140 430 7 8 TYPE 1 Maximum 400 ...

Страница 195: ...Chapter 9 Peripheral Devices 9 14 TYPE 2 Maximum 600 Watt TYPE 3 4 5 A ...

Страница 196: ... 9 15 9 1 4 IS7 Remote cable options 1 Components Keypad Bracket Remote cable 2 Keypad bracket drawings 2 Remote cable 1 Product code Product code Product Name Note 64110009 INV IS7 REMOTE CABLE 2M 64110010 INV IS7 REMOTE CABLE 3M ...

Страница 197: ... cable and use after connect the other side of cable to the product Note 1 When you use remote cable at unspecified products you must use only the specified because keypad may lead to malfunction by power supply voltage drop and inflow noise 2 After connecting the remote cable if unusually display at LCD keypad as line check cable may be in poor contact so please check 2M 3M ...

Страница 198: ...on is STO function to cut off power supply from motor Cutting off inverter output current by impeding gate with hard wired and not to cause a torque STO Safety Torque Off IEC61800 5 2 STO function has 2 channels SFT1 SFT2 the input signal is connected to independently The signal cut off the output of the inverter control circuit drive signal and power module During operation safety function is act...

Страница 199: ...1 Example of safety input wiring 2 0 75 160KW Product Installation EX 3 7KW Product Open top cover and equip safety option at slot 2 Connect safety option and power part of inverter with wire Safety Function Terminal 24S SE 24S SP SR SR ...

Страница 200: ...Type Twisted pare Wire 24Vdc Max 10mA SE Safety Input 1 SFT1 Short Safety Function Stop 24SE SE or SP Open Safety Function Operation 24SE SP or SP SP Safety Input 2 SFT2 SR SR Complete Output Relay Safety Features DC24V 5Abelow B contact Caution The length of wiring safety input terminal is not used for more than 30m Safety Function can malfunction during operation 24SE SE SFT1 24S SP SFT2 SR SR S...

Страница 201: ...orske Veritas Classification CERTIFICATE NO E 11815 11 1 3 Classification Model SV iS7 Products SV 008 iS7 2 N O F D W L S Inverter Capacity of Applied Motor Serie s Nam e Input Voltage Keypad UL EMC DCR CLASS 0008 0 75 kW Wide Use Inverter 2 3 Phase 200 230 V 4 3 Phase 380 480 V N NONE S GLCD Graphic Loader O OPEN E Enclos ed UL Type1 note1 P Enclosed ULType 12 Blank Non EMC F EMC Blank Non DCR D...

Страница 202: ...tion Produt 12 2 Note1 Enclosed UL Type 1 has the conduit option addtionally at 0 75 to 75 kW products Note2 DB Resistor of IS7 Product is the option of WEB product Applicable capacity is from 0 75 to 375 kW of IS7 products ...

Страница 203: ...e the DC bus ripple becomes 120 Hz and the VFDs DC bus circuit is subject to higher stress in order to deliver equivalent power Additionally input currents and harmonics increase beyond those encountered with three phase input Input current distortion of 90 THD and greater can be expected under single phase input compared to approximately 40 with three phase input as indicated in Figure 2 Therefor...

Страница 204: ...t only The AC supply voltage must be within the required voltage range of 240 480Vac 10 to 5 to maximize motor power production Standard product with three phase voltage input as an allowable range of 10 to 15 Therefore a stricter input voltage tolerance of 10 to 5 applies when using the drive with a single phase supply The average bus voltage with single phase input is lower than the equivalent o...

Страница 205: ...C 40a 7 5kW 10 16 23 28 6 41 2 8 8 63 UTS150 60A MC 50a 11kW 15 24 31 44 3 54 7 6 6 80 UTS150 100A MC 65a 15kW 20 31 38 55 9 69 7 4 4 100 UTS150 125A MC 100a 18 5kW 25 38 45 70 8 82 9 2 2 125 UTS150 150A MC 130a 22kW 30 45 64 85 3 116 1 1 1 160 UTS250 175A MC 150a 30kW 40 60 75 121 0 152 0 1 0 1 0 200 0 24 200 UTS250 225A MC 150a 37kW 50 75 93 154 0 190 0 2 0 2 0 250 0 2 240 UTS400 300A MC 225a 45...

Страница 206: ... 1 3 2 3 6 5 7 14 14 10 UTE100 15A MC 9b 2 2kW 3 2 8 4 1 5 5 7 7 14 14 15 UTE100 15A MC 12b 3 7kW 5 4 1 6 1 7 5 11 1 14 14 20 UTE100 15A MC 18b 5 5kW 7 5 6 1 8 0 11 0 14 7 12 12 32 UTE100 30A MC 22b 7 5kW 10 8 1 12 14 4 21 9 12 12 35 UTE100 30A MC 32a 11kW 15 12 16 22 0 26 4 10 10 50 UTS150 50A MC 40a 15kW 20 16 20 26 6 35 5 8 8 63 UTS150 60A MC 50a 18 5kW 25 20 23 35 6 41 1 6 6 70 UTS150 80A MC 6...

Страница 207: ...es 2014 35 EU Directive of the European Parliament and of the Council on the harmonisation of the laws of the Member States relating to the making available on the market of electrical equipment designed for use within certain voltage limits 2014 30 EU Directive of the European Parliament and of the Council on the harmonisation of the laws of the Member States relating to electromagnetic compatibi...

Страница 208: ...be fitted as closely as possible to the incoming mains supply of the wiring enclousure usually directly after the enclousures circuit breaker or supply switch 3 The back panel of the wiring cabinet of board should be prepared for the mounting dimensions of the filter Care should be taken to remove any paint etc from the mounting holes and face area of the panel to ensure the best possible earthing...

Страница 209: ...800 3 C3 iS7 series Standard Filters INVERTER POWER CODE CURRENT VOLTAGE LEAKAGE CURRENT DIMENSIONS L W H MOUNTING Y X WEIGHT MOUNT FIG OUTPUT CHOKES THREE PHASE NOM MAX SV0300iS7 4 30kW SV0370iS7 4 37kW FE T100 2 100A 220 480VAC 1 3mA 150mA 420 x 200 x 130 408 x 166 13 8 Kg A FS 3 SV0450iS7 4 45kW SV0550iS7 4 55kW FEP T150 150A 220 480VAC 1 3mA 150mA 332 x 170 x 120 115 x 155 8 Kg B FS 3 SV0750iS...

Страница 210: ...nclude the Machinery Directive for machine manufacturers the LowVoltage Directive for electronics manufacturersand the EMC guidelinesfor safe noise control LowVoltage Directive We have confirmed thatour products complywith the LowVoltage Directive EN 61800 5 1 EMCDirective The Directive definesthe requirementsfor immunityand emissionsof electrical equipmentused within the European Union The EMCpro...

Страница 211: ...he following cases the service will be charged The failure occurred from the consumer s improper storage handling and careless handling The failure occurred from the consumer s error in the design of software or hardward The failure occurred from the error of power source and the defect of the connector The failure occurred from the force majeure fire flood gas disaster earthquake etc The product ...

Страница 212: ...ne 9 2013 06 9th edition S W Updated 10 2014 01 10th edition Revise CI logo Add UL description 11 2014 03 11th edition S W version contents updated 12 2015 04 12th edition Correct errors and add omissions 2015 S W version contents updated 13 2015 07 13th Edition Add UL Single Phase Rating Chapter LSIS regards the environmental preservation as a high priority and all our employees do our best for t...

Отзывы: