Chapter 8 Table of Functions
8-10
No. Comm. No. Function Display
Name
Setting Range
Initial Value
Shift in
Operation
Control Mode
V/F
SL VC
SLT
VC
T
76
Note15)
0h134C
CompFreq
Limit
Restriction of
compensational
frequency of
regeneration anc
avoidance for
press
0 ~ 10.00 [Hz]
1.00 [Hz]
X
O O O X X
77 0h134D
RegenAvd
Pgain
P-gain of
regeneration anc
avoidance for
press
0 ~ 100.0 [%]
50.0 [%]
O
O O O X X
78 0h134E
RegenAvd
Igain
I-gain of
regeneration anc
avoidance for
press
20 ~ 30000 [ms]
500 [ms]
O
O O O X X
79
0h134F
DB Turn On Lev DB Unit Operating Voltage 200V : 350~400[V]
390[V]
X
O O O O O
400V : 600~800[V]
780[V]
80
0h1350 Fire Mode Sel
Fire Function Select
0 None
0:None
X
O O O X X
1 Fire Mode
2 Fire Test
81
주
16) 0h1351 Fire Mode Freq
Fire Mode Frequency
0~Max Freq[Hz]
60.00
X
O O O X X
82
0h1352 Fireq Mode Dir
Fire Mode Operating
Direction
0 Forward
0:Forward
X
O O O X X
1 Reverse
83
-
Fire Mode Cnt
Fire Mode Counter
0~99
0
X
O O O X X
* The grey code refers to hidden code, emerging only in case of setting of the code.
Note 14)
ADV-71~72 is displayed only when ADV-70 (Run En Mode) is set as “DI Dependent”.
Note15)
ADV-76~78 is displayed only when ADV-75 (RegenAvd Sel) is set as “Yes”.
Note 16)
ADV-81~83 is displayed only when it is set as “Fire Mode” or “Fire Test” at ADV-80.