Chapter 8 Table of Functions
8-14
No. Comm. No.
Function
Display
Name
Setting Range Initial Value
Shift in
Opera-tion
1)Control Mode
V/F
SL VC
SLT
VC
T
58
0h143A
Trq Bias
Src
torque bias
setting method
0 Keypad-1
0:Keypa
d-1 X
X X O X X
1 Keypad-2
2 V1
3 I1
4 V2
5 I2
6 Int 485
7 FiedBus
8 PLC
59
0h143B
Torque
Bias
torque bias
-120 ~ 120
[%]
0.0 O
X X O X X
60
0h143C
Torque
Bias FF
torque bias
compensation
0 ~ 100 [%]
0.0 O
X X O X X
62
0h143E
Speed
Lmt Src
Speed limit setting
method
0 Keypad-1
0:Keypa
d-1 O
X X X X O
1 Keypad-2
2 V1
3 I1
4 V2
5 I2
6 Int 485
7 FiedBus
8 PLC
63
0h143F FWD Speed
Lmt
forward speed limit
0 ~ max.
freq.[Hz] 60.00
O
X X X X O
64
0h1440
REV Speed
Lmt
reverse speed limit
O
X X X X O
65
0h1441 Speed Lmt
Gain
Speed limit
operation gain
100 ~ 5000
[%]
500
O
X X X X O
66
0h1442
Droop
Perc
droop operation
amount
0 ~ 100 [%]
0.0
O
X X X X O
67
Note19)
0h1443
Droop St
Trq
droop start torque
0 ~ 100 [%] 100.0
O
X X X X O
68
0h1444 SPD/TRQ
Acc T
torque
mode
speed
mode exchange
accelerating time
0 ~ 600 [s]
20.0
O
X X X X O
69
0h1445 SPD/TRQ
Acc T
torque
mode
speed
mode exchange
decelerating time
30.0
O
X X X X O