Chapter 8 Table of Functions
8-39
No.
Comm. No.
Function
Display
Name
Setting Range
Initial
Value
Shift in
Operation
Control Mode
V/F
SL VC
SLT
VC
T
51
0h1B33 Stall Freq 1
stall frequency 1
Start frequency 1
~ Stall frequency 1 [Hz]
60.00
O
O O X
O
X
52
0h1B34
Stall Level 1 stall level 1
30 ~ 250 [%] 180
X
O
O
X
O
X
53
0h1B35
Stall Freq 2 stall frequency 2
stall frequency 1
~ stall frequency 2[Hz] 60.00
O
O
O
X
O
X
54
0h1B36
Stall Level 2 stall level 2
30 ~ 250 [%] 180
X
O
O
X
O
X
55
0h1B37
Stall Freq 3 stall frequency 3
stall frequency 2
~ stall frequency 4[Hz] 60.00
O
O
O
X
O
X
56
0h1B38
Stall Level 3 stall level 3
30 ~ 250 [%] 180
X
O
O
X
O
X
57
0h1B39
Stall Freq 4 stall frequency 4
stall frequency 3
~ max. freq.[Hz] 60.00
O
O
O
X
O
X
58
0h1B3A
Stall Level 4 stall level 4
30 ~ 250 [%] 180
X
O
O
X
O
X
66
0h1B42
DB Warn %ED DB resistance warning
level
0 ~ 30 [%]
0
O
O
O
O
O
O
70
0h1B46
Over SPD
Freq
overspeed judgment
frequency
20 ~ 130 [%] 120.0
O
X
X
O
X
O
72
0h1B48
Over SPD
Time
overspeed judgment time 0.01 ~ 10.00 [s] 0.01
O
X
X
O
X
O
73
0h1B49
Speed Dev
Trip
speed error failure
0 No
0 : No
O
X
X
O
X
X
1 Yes
74
0h1B4A
Speed Dev
Band
speed error width
2 ~ max.
freq.[Hz] 20.00
O
X
X
O
X
X
75
0h1B4B
Speed Dev
Time
speed error judgment
time
0.1 ~ 1000.0 [s]
1.0
O
X
X
O
X
X
77
0h1B4D
Enc Wire
Check
Encoder option
connection check
0 No
0 : No
O
X
X
O
X
O
1 Yes
78
0h1B4E
Enc Check
Time
Encoder connection
check time
0.1 ~ 1000.0 [s] 1.0
O
X
X
O
X
O
79
0h1B4F
FAN Trip Mode cooling fan failure
selection
0 Trip
0 : Trip
O
O
O
O
O
O
1 Warning
80
0h1B50
Opt Trip Mode movement selection in
case of option trip
0 None
1 :
Free-
Run
O
O
O
O
O
O
1 Free-Run
2 Dec
81
0h1B51
LVT Delay low voltage failure
judgment delay time
0 ~ 60.0 [s] 0.0
X
O
O
O
O
O
82
0h1B52
LV2 Enable
Choose
low-
voltage operation
failure
0
No
0:No
X
O O O O O
1
Yes
* The grey code refers to hidden code, emerging only in case of setting of the code.
Note 38)
PRT-10 code is displayed only when PRT-09(Retry Number) is set the value more than “0”.
Note 39)
PRT-13~15 codes are displayed only when PRT-12(Lost Cmd Mode) is not set as “NONE”.
Содержание SV0008iS7-2
Страница 20: ...Chapter 1 Basics 1 5 ...
Страница 54: ...Chapter 3 Installation 3 28 ...
Страница 181: ...Chapter 8 Table of Functions 8 46 ...
Страница 195: ...Chapter 9 Peripheral Devices 9 14 TYPE 2 Maximum 600 Watt TYPE 3 4 5 A ...