Chapter 8 Table of Functions
8-25
8.1.7 Parameter mode – Communication function group (
COM)
No. Comm. No. Function Display
Name
Setting Range
Initial
Value
Shift in
Operation
Control Mode
V/F
SL VC
SLT
VC
T
00
-
Jump Code jump code
0 ~ 99
20 O
O
O
O
O
O
01
0h1701
Int485 St ID built-in communication
inverter ID
1 ~ 250
1 O
O
O
O
O
O
02
0h1702 Int485 Proto built-in communication
protocol
0 ModBus RTU
0:
ModBus
RTU
O
O
O
O
O
O
1 --Reserved --
2 Serial Debug
03
0h1703
Int485
BaudR
built-in communication
speed
0 1200 bps
3:
9600
bps
O
O
O
O
O
O
1 2400 bps
2 4800 bps
3 9600 bps
4 19200 bps
5 38400 bps
04
0h1704 Int485 Mode built-in communication
frame setting
0 D8/PN/S1
0:
D8/PN/S
1
-
O
O
O
O
O
1 D8/PN/S2
2 D8/PE/S1
3 D8/PO/S1
05
0h1705
Resp Delay Transmission delay after
reception
0 ~ 1000 [ms] 5ms O
O
O
O
O
O
06
Note27)
0h1706
FBus S/W
Ver
communication option S/W
version
-
1.00 O
O
O
O
O
O
07
0h1707
FBus ID communication option
inverter ID
0 ~ 255
1 O
O
O
O
O
O
08
0h1708
FBUS
BaudRate
FBus communication
speed
-
12Mbps
-
O
O
O
O
O
09
0h1709
FieldBus
LED
communication option LED
status
-
-
O
O
O
O
O
O
30
0h171E ParaStatus Num
-
0 ~ 8
3 O
O
O
O
O
O
31
0h171F
Para Stauts-1
ou
tp
ut
a
dd
re
ss
1
0000 ~ FFFF Hex
000A O
O
O
O
O
O
32
0h1720
Para Stauts-2
2
000E O
O
O
O
O
O
33
0h1721
Para Stauts-3
3
000F O
O
O
O
O
O
34
0h1722
Para Stauts-4
4
0000 O
O
O
O
O
O
35
0h1723
Para Stauts-5
5
0000 O
O
O
O
O
O
36
0h1724
Para Stauts-6
6
0000 O
O
O
O
O
O
37
0h1725
Para Stauts-7
7
0000 O
O
O
O
O
O
38
0h1726
Para Stauts-8
8
0000 O
O
O
O
O
O
* The grey code refers to hidden code, emerging only in case of setting of the code.
Note 27)
COM 06~17 codes are displayed only when the communication option card is