Chapter 8 Table of Functions
8-15
* The grey code refers to hidden code, emerging only in case of setting of the code.
Note 19)
CON-67 is displayed only when Encoder option board is mounted.
No. Comm. No. Function
Display
Name
Setting Range
Initial Value
Shift in
Operation
1)Control Mode
V/F
SL VC
SLT
VC
T
70
0h1446
SS Mode
Speed search
mode selection
0
Flying Start-1
0
X
O
O
O
X
X
1
Flying Start-2
71 0h1447 Speed
Search
Speed search
operation selection
Bit 0000 ~ 1111
0000
X
O
O
O
X
X
1
accelerating speed
search selection
2
Reset start after trip
3
Re-start after
instantaneous
interruption
4
Start immediately after
power ON
72
Note20)
0h1448 SS Sup-
Current
speed search
standard current
80 ~ 200 [%]
Below
75kW 150
O
O
O
X
X
X
Above
90kW 100
73 0h1449 SS P-Gain speed search
proportional gain
0 ~ 9999
100 O
O
O
X
X
X
74 0h144A SS I-Gain
speed search
integral calculus
gain
0 ~ 9999
200 O
O
O
X
X
X
75 0h144B SS
Block Time
Pre-speed search
output
block time
0 ~ 60 [s]
1.0 X
O
O
X
X
X
77 0h144D KEB Select
energy buffering selection
0 None
0:None X
O O O X X
1 KEB-1
2 KEB-2
78
Note20)
0h144E
KEB Start
Lev
energy buffering
start amount
110 ~ 200 [%]
125.0 X
O
O
O
X
X
79 0h144F KEB Stop
Lev
energy buffering
stop amount
125 ~ 210 [%]
130.0 X
O
O
O
X
X
82
Note21)
0h1452
ZSD
Frequency
permanent
detection
frequency
0 ~ 10 [Hz]
2.00 O
X
X
O
X
O
83 0h1453 ZSD Band
permanent
detection
frequency band
0 ~ 2 [Hz]
1.00 O
X
X
O
X
O
86
Note
22)
0h1456 KEB P Gain Energy Buffering P Gain
0~20000
1000 O
O O O X X