![LS SV0008iS7-2 Скачать руководство пользователя страница 136](http://html1.mh-extra.com/html/ls/sv0008is7-2/sv0008is7-2_manual_1943740136.webp)
Chapter 8 Table of Functions
8-1
8.1 Table of Functions
8.1.1 Parameter mode – DRV group(
DRV)
* The number of page is for User’s manual uploaded at LSIS website. You can
download the User’s manual which is described detailed function of parameter from
website. (http://www.lsis.com )
No. Comm. No.
Function
Display
Name
Setting Range
Initial Value
Shift in
Operation
Note1)
Control Mode
V/F
SL VC
SLT
VC
T
00
-
Jump Code jump code
1 ~ 99
9 O
O O O O O
01 0h1101
Cmd
Frequency target frequency
Start freq.~ max.
freq.[Hz]
0.0 O
O O O X X
02 0h1102 Cmd Torque torque command
-180 ~ 180 [%]
0.0 O
X X X O O
03 0h1103
Acc Time accelerating time
0 ~ 600 [s]
Below 75kW
20.0
O
O O O O O
Above 90kW
60.0
04 0h1104 Dec Time decelerating time
0 ~ 600 [s]
Below 75kW
30.0 O O O O O O
Above 90kW
90.0
06 0h1106 Cmd Source
operating
command
method
0 Keypad
1 : Fx/Rx-1 X
O O O O O
1 Fx/Rx-1
2 Fx/Rx-2
3 Int 485
4 Field Bus
5 PLC
07 0h1107 Freq Ref Src frequency setting
method
0 Keypad-1
0 : Keypad-1 X
O O O X X
08 0h1108 Trq Ref Src torque command
method
0 Keypad-1
0 : Keypad-1 X
X X X O O
1 Keypad-2
2 V1
3 I1
4 V2
5 I2
6 Int 485
7 Encoder
8 Fied Bus
9 PLC
09
Note1)
0h1109
Control
Mode
control mode
0 V/F
0 : V/F X
O O O O O
1 V/F PG
2
Slip Compen
3
Sensorless-1
4
Sensorless-2
5 Vector
* The grey code refers to hidden code, emerging only in case of setting of the code.
Note 1)
Effectiveness of each code according to the Control Mode setting
Refer to Option manual for options.
Control mode abbreviation: V/F: V/F (PG included), SL: Sensorless-1, 2, VC: Vector,
SLT: Sensorless-1, 2 Torque, VCT: Vector Torque