Chapter 8 Table of Functions
8-35
8.1.10
Parameter mode – Option card function group (
APO)
No. Comm. No. Function
Display
Name
Setting Range
Initial
Value
Shift in
Operation
Control Mode
V/F
SL VC
SLT
VC
T
00
-
Jump Code jump code
0 ~ 99 20
O
O
O
O
O
O
01
Note35)
0h1A01
Enc
Opt Mode encoder function item
0 None
0:Non
e
O
O
O
O
O
O
1 Feed-Back
2 Reference
04 0h1A04
Enc
Type Sel encoder type selection
0 Line Driver
0 :
Line
Driver
X
O
O
O
O
O
1 Totem or Com
2 Open Collector
05 0h1A05
Enc
Pulse Sel encoder pulse direction
0 (A+B)
0 :
(A+B)
X
O
O
O
O
O
1 -(A+B)
2 A
06 0h1A06
Enc
Pulse Num Number of encoder pulses
10 ~ 4096 1024
X
O
O
O
O
O
08 0h1A08 Enc Monitor Feed Back monitor
-
-
O
O
O
O
O
O
09 0h1A09 Pulse Monitor Reference monitor
-
-
O
O
O
O
O
O
10 0h1A0A Enc Filter encoder input filter
0 ~ 10000 [ms]
3
O
O
O
O
O
O
11 0h1A0B Enc Pulse x1 Enc input minimum pulse
0 ~ 100 [kHz] 0.0
O
O
X
O
X
O
12 0h1A0C Enc Perc y1 output% at Enc minimum pulse
0 ~ 100 [%] 0.00
O
O
X
O
X
O
13 0h1A0D Enc Pulse x2 Enc input maximum pulse
0 ~ 200 [kHz] 100
O
O
X
O
X
O
14 0h1A0E Enc Perc y2 Enc maximum pulse
시
output%
0 ~ 100 [%] 100
O
O
X
O
X
O
20
Note36)
0h1A14 Aux Motor Run display of number of auxiliary motor
movement
0 ~ 4
0
O
O
O
O
X
X
21 0h1A15 Starting Aux starting auxiliary motor selection
1 ~ 4
1
X
O
O
O
X
X
22 0h1A16 AutoOp Time auto change operation time
XX:XX [Min] 0:00
O
O
O
O
X
X
23 0h1A17 Start Freq 1 1st auxiliary motor Start frequency
0 ~ 60[Hz]
49.99
O
O
O
O
X
X
24 0h1A18 Start Freq 2 2nd auxiliary motor Start frequency
O
O
O
O
X
X
25 0h1A19 Start Freq 3 3nd auxiliary motor Start frequency
O
O
O
O
X
X
26 0h1A1A Start Freq 4 4thauxiliary motor Start frequency
O
O
O
O
X
X
27 0h1A1B Stop Freq 1 1st auxiliary motor stop frequency
15.00
O
O
O
O
X
X
28 0h1A1C Stop Freq 2 2nd auxiliary motor stop frequency
O
O
O
O
X
X
29 0h1A1D Stop Freq 3 3nd auxiliary motor stop frequency
O
O
O
O
X
X
30 0h1A1E Stop Freq 4 4th auxiliary motor stop frequency
O
O
O
O
X
X
31 0h1A1F Aux Start DT auxiliary motor starting delay time
0 ~ 3600.0 [s] 60.0
O
O
O
O
X
X
32 0h1A20 Aux Stop DT auxiliary motor stop delay time
O
O
O
O
X
X
33 0h1A21 Num of Aux auxiliary motor number selection
0 ~ 4
4
X
O
O
O
X
X
34 0h1A22 Regul Bypass bypass selection
0 No
0 : No
X
O
O
O
X
X
1 Yes
35 0h1A23 Auto Ch Mode auto change mode selection
0 None
1: Aux
X
O
O
O
X
X
Содержание SV0008iS7-2
Страница 20: ...Chapter 1 Basics 1 5 ...
Страница 54: ...Chapter 3 Installation 3 28 ...
Страница 181: ...Chapter 8 Table of Functions 8 46 ...
Страница 195: ...Chapter 9 Peripheral Devices 9 14 TYPE 2 Maximum 600 Watt TYPE 3 4 5 A ...