Chapter 6 Basic Functions
6-18
IN-89 In Check Time : when using multi-function input terminal as setting multi-acc/dec,
you can set up the time for checking terminal input inside the inverter.
For example, if you set terminal input check time for 100msec and multi-function P6 is
entered, you can check if other terminal input is entered for 100msec.
After 100mse, the P6 terminal related to the acc/dec time is set.
4) Acc/Dec time Set by Setting the Acc/Dec Time of Switching Frequency
Group
Code
No.
Function Display
Setting
Display
Setting Range
Unit
DRV
03
Acc Time
-
10.0
0~600
sec
04
Dec Time
-
10.0
0~600
sec
BAS
70
Acc Time-1
-
20.0
0~600
sec
71
Dec Time-1
-
20.0
0~600
sec
ADV
60
Xcel Change Fr
-
30.00
0~Max Freq
Hz/RPM
You can Change the slop of acc/dec without the use of multi-function terminal.
Inverter operates as a slop set at BAS-70 and 71 if operating frequency is less
switching frequency at ADV-60. However, if operating frequency increases more than
acc/dec switching frequency, inverter operates as a slop set at DRV-03 and 04.
If you set multi-function input terminal as multi-acc/dec(XCEL-L and XCEL-M), inverter
operates with multi-acc/dec input regardless of the acc/dec switching frequency.