Chapter 12. Protective Function
12-4
12.5
Frequency command loss
Group
Code Parameter Name
Setting
Range
Initial
Unit
P65
Criteria for analogue input signal
0
0 ~ 2
0
P81
Drive mode select after loss of
frequency command
-
0 ~ 2
0
P82
Wait time after loss of frequency
command
- 0.1~120
1.0
sec
PG Group
P77
Multi-function relay select
11
0 ~ 18
17
Select the Drive mode when frequency reference set via analog signal or communication option is lost.
P65: Set the criteria for analog input signal loss.
0 Disabled
1
When half the value set in P56 and P61 is entered
P65
Criteria for analogue
input signal loss
2
When less than the value set in P56 and P61 is entered
If frequency command is set to 3(V1 of terminal) in Frq code of Drive Group and P65 is set to 1 and when
AI is less than half the value set in P56, it determines frequency command loss. At the moment, if entering
current based on the value converting 0~10V to 0~100%, it operates with the value converting 0~20mA to
0~100%.
i.e.) Voltage input: If P56 and P65 are set to 50% and 2 respectively, it operates at 5V.
Current input: If P56 and P65 are set to 50% and 1 respectively, it operates at 5mA.
P81: When the conditions set in P65 are met for the time set in P82, the inverter operates as follows.
0
Continuous operation with the frequency before
command loss occurs
1
Free run stop (output cut off)
P81
Drive mode select after
loss of frequency
command
2 Decel
to
stop
P77: Multi-function relay output (30AC) is used to output information on loss of frequency command to
external sequence.