Chapter 9. Basic Functions
9-10
Note
If the target frequency is less than 40% of the max. frequency as below figure, it may not realize a complete s-
shape pattern run with the ending partially cut.
Frequency
Target
frequency
Max.
frequency
Time
z
Accel/Decel Disable
Group
Code Parameter Name
Setting
Range
Initial
Unit
P66
Multi-function input terminal P1 define - 0
~ ~
PG Group
P70
Multi-function input terminal P5 define
23
0 ~ 24
4
Select one terminal among Multi-function input terminals P1-P5 to define Accel/Decel disable.
If P5 is selected, set P70 to 23 to activate this function.