Chapter 10. Advanced Functions
10-2
z
Starting DC brake
Group
Code Parameter Name
Setting
Range
Initial
Unit
P13
DC brake start voltage
-
0 ~ 200
50
%
PG Group
P14
DC brake start time
-
0 ~ 60
0
sec
P13 : It sets the level as a percent of Motor rated current.
P14 : Motor accelerates after DC voltage is applied for the set time.
Caution
If excessive DC Brake voltage is set or DC Brake time is set too long, it may cause motor overheating and
damage to the motor.
Setting P13 or P14 to 0 will disable Starting DC brake.
t : After P14, the frequency starts accelerating.
z
DC brake at a stop
Group
Code Parameter Name
Setting
Range
Initial Unit
PG Group
P13
DC brake start voltage
-
0 ~ 200
50
%
PG Group
P68
Multi-function input terminal P3 function
select
11
0 ~ 24
2
P13 : It sets the level as a percent of Motor rated current.
Select a terminal to issue a command of DC brake at a stop among P1 to P5.
If P3 terminal is set for this function, set P68 to 11(DC brake at a stop).
Caution
If excessive DC Brake voltage at a stop is set or DC Brake time is set too long, it may cause motor overheating
and damage to the motor.
Frequency
Voltage
Operation
command
P14 t