Chapter 3. Wiring
3-3
3.4
Control Terminal Wiring Specification
Terminal description
COM optional terminal
P1 P2 P3 P4 P5 VR AI AM CM
S+ S-
T/M
Terminal description
Wire size
Torque [lb-in]
Remarks
P1~P5 Multi-function
input
T/M
1-5
22
AWG,0.3
mm
2
3.0
VR
Power T/M for external volume resistance
22 AWG,0.3 mm
2
3.0
AI
Analogue frequency input T/M
22 AWG,0.3 mm
2
3.0
AM Multi-function
output
T/M
22
AWG,0.3
mm
2
3.0
CM Common
terminal
22
AWG,0.3
mm
2
3.0
Multi-function Relay T/M Spec.
30A 30B 30C
T/M
Terminal description
Wire size
Torque[lb-in]
Remarks
30A
Multi-function relay output A contact
20 AWG,0.5 mm
2
4.5
30B
Multi-function relay output B contact
20 AWG,0.5 mm
2
4.5
30C
Common for Multi-function relays
20 AWG,0.5 mm
2
4.5
CAUTION
Tie the control wires more than 15cm away from the control terminals. Otherwise, it interferes with front cover
reinstallation.
Note
When you use external power supply (24V) for multi-function input terminal (P1~P5), terminals will be active
above 12V level. Take caution not to drop the voltage below 12V.