Chapter 10. Advanced Functions
10-8
10.7
PI
Control
Group
Code Parameter Name
Setting
Range
Initial Unit
P46
Control mode select
2
0 ~ 3
0
-
P47
P gain for PI controller
-
0 ~ 999.9
300.0
%
P48
Differential time for PI controller(I gain)
-
0.1~ 32.0
1.0
sec
P50
Feed forward gain for PI controller
0 ~ 999.9
0
%
P51
PI output frequency upper limit
-
0 ~ 200
60.0
Hz
P52
PI output frequency lower limit
0 ~ 200
0.5
Hz
PG Group
P66~
P70
Multi-function input terminal P1 ~ P5 define 20
0 ~ 24
-
-
Set P46 to 2(PI control).
Output frequency of the inverter is controlled by PI control for use as constant control of flow, pressure or
temperature.
P47: Set the percentage of output to error. If P Gain is set to 50%, 50% of the error value will be output.
Higher value can reach the target control value faster but it may cause oscillation.
P48: Set the time to output the accumulated error value. Set the time required to output 100% when the
error value is 100%. If differential time is set to 1 second and error is 100%, it outputs 100% in 1 second. If
the value is reduced, response will be faster but setting too low may lead to controller oscillation.
P50: Set the gain to add the target value to the PI controller output.
P51, P52: It limits the output of the PI controller.
P66 ~ P70: To exchange PI to normal operation, set one of P1~P5 terminal to 20 and turn ON.