Chapter 10. Advanced Functions
10-5
10.4
3-Wire
operation
Group
Code Parameter Name
Setting
Range
Initial
Unit
P66 Multi-function
Input
terminal P1 select]
0
0
~ ~
PG Group
P70
Multi-function Input terminal P5 select
17
0 ~ 24
4
Select a terminal from P1-P5 for use as 3-Wire operation.
If P5 is selected, set P70 to 17(3-Wire operation).
Input signal is latched (saved) in 3-Wire operation. Therefore, inverter can be operated by Push-button
switch.
The bandwidth of pulse (t) should not be less than 50msec.
10.5
Dwell
operation
Group
Code Parameter Name
Setting
Range
Initial
Unit
P31
Dwell frequency
-
0 ~ 200
5.0
Hz
PG Group
P32
Dwell time
-
0 ~ 10
0.0
sec
In this setting, a motor begins to accelerate after dwell operation is executed for dwell time at the specified
dwell frequency.
It is mainly used to release mechanical brake in elevators after operating at dwell frequency.
Dwell frequency: This function is used to output torque in an intended direction. It is useful in hoisting
applications to get enough torque before releasing a mechanical brake. Rated Slip frequency is calculated
by the formula shown below.
P1
P2
P5
CM
FX : P66 = 0
RX : P67 = 1
3-Wire : P70 = 17
FX
RX
Frequency
P5 (3-Wire)
t