Chapter 10. Advanced Functions
10-6
⎟
⎠
⎞
⎜
⎝
⎛
×
−
=
120
P
rpm
f
f
r
s
where,
s
f
= rated slip frequency
r
f
= rated frequency
rpm
= motor rated rpm
P
= no. of motor poles
i.e.) rated frequency: 60Hz, rated rpm: 1740rpm, No. of poles: 4
Hz
f
s
2
120
4
1740
60
=
⎟
⎠
⎞
⎜
⎝
⎛
×
−
=
Frequency
Operation
command
Dwell time
Dwell frequency
Start frequency
10.6
Slip Compensation Control
Group
Code Parameter Name
Setting Range
Initial
Unit
P40
Motor type select
-
0.1 ~ 0.4
-
P41
No. of motor poles
-
2 ~ 12
4
P42
Rated slip frequency
-
0 ~ 10
-
Hz
P43
Motor rated current
-
0.0 ~ 25.5
-
A
P44
Motor no load current
-
0.0 ~ 25.5
-
A
PG Group
P46
Control mode select
1
0 ~ 2
0
Set P46 to 1(Slip compensation control).
This function enables the motor to run in constant speed by compensating inherent slip in an induction
motor.
P46: Set the motor type connected to the inverter output side.
0.1 0.1kW
0.2 0.2kW
P46 Motor
type
select
0.4 0.4kW
Содержание SV-iE5 Series