Chapter 10. Advanced Functions
10-1
10.
Advanced Functions
10.1
DC
Brake
z
Stopping motor by DC brake
Group
Code Parameter Name
Setting
Range
Initial
Unit
P 8
Stop mode select
1
0 ~ 2
0
P 9
DC brake start frequency
-
0 ~ 60
5.0
Hz
P10
DC brake wait time
-
0 ~ 60
0.1
sec
P11
DC brake voltage
-
0 ~ 200
50
%
PG Group
P12
DC brake time
-
0 ~ 60
1.0
sec
Select 1 in P8 code(DC brake stopping) of PG Group
P 9 : The frequency at which the DC brake will become active
P10 : Inverter output will hold for this time before applying DC brake voltage.
P11 : Set this value as a percent of Motor rated current.
P12 : Sets the time for DC brake voltage to be applied to the motor.
Caution
If excessive DC Brake voltage is set or DC Brake time is set too long, it may cause motor overheating and
damage to the motor.
Setting P11 or P12 to 0 will disable DC brake.
DC Brake Wait time: When load inertia is large, DC brake start frequency is high or excessive DC
voltage is allowed to motor, over current trip may occur. It can be prevented using P10 before starting DC
brake.
Freuency
Operation
command
Voltage
Current
P 9
P10 P12
P11