Chapter 9. Basic Functions
9-11
9.5
V/F Control
z
Linear V/F pattern operation
Group
Code Parameter Name
Setting
Range
Initial
Unit
P17
Base frequency
-
30 ~ 200
60.0
Hz
P18
Start frequency
-
0.1 ~ 10
0.5
Hz
PG Group
P22
V/F pattern
0
0 ~ 1
0
Set P22 code to 0(linear)
This pattern maintains a linear volts/frequency ratio by voltage/frequency(V/F).
Base frequency: Inverter outputs its rated voltage at this level. Enter the motor nameplate frequency.
Start frequency: Inverter starts to output its voltage at this level.
Operation
command
Frequency
Start frequency
Base frequency
Voltage
Inverter
rated voltage
Time
Time