Pre-Commissioning
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp.
Function
Range
Description
Test Run
Cooling Test Run
7HVWUXQRSHUDWHV0XOWL9V\VWHPVLQFRROLQJPRGHIRUD
maximum of 18 minutes.
3 Minute Delay
N / A
Only for factory testing; cannot change standby timer
compressor restart after thermo-off.
Select
Temperature
Sensor
Control Standard
• Air Temperature (Air)
• Leaving Water Temp.
(Water) (Default)
Sensor Location
• Remote Control
• Indoor Unit
Selects the reference sensor (air / water) for control.
Dry Contact Mode
• Manual
• Auto (Default)
Selects the initial state of the Hydro Kit when a dry
contact signal is input.
Central Control
Address
Hexadecimal address
• 00~FF (Default: 00)
Use for address assigning when a Central Controller is
installed.
Override Master /
Slave
• Master
• Slave (Default)
Prevents the Hydro Kit operating in a different mode. If
a Hydro Kit is set as Slave, it cannot switch to the
opposite operating mode (cooling / heating).
Pump Test Run
Test Run
Checks if water circulation is normal.
Air Cooling Set
Temp.
• Upper Limit: 75°F~86°F (24°C~30°C) (Default: 86°F [30°C])
• Lower Limit: 61°F~72°F (16°C~22°C (Default: 64°F [18°C])
Adjusts range of the "Setting Air Temperature" for
cooling mode.
Water Cooling Set
Temp.
Fan Coil Unit is NOT Installed
• Upper Limit: 68°F~77°F (20°C~25°C) (Default: 75°F [24°C])
• Lower Limit: 61°F~68°F (16°C~20°C) (Default: 61°F [16°C])
Fan Coil Unit IS Installed
• Upper Limit: 68°F~77°F (20°C~25°C) (Default: 75.2°F [24°C])
• Lower Limit: 41°F~68°F (5°C~20°C) (Default: 41°F [5°C])
Adjusts range of the "Setting Leaving Water
Temperature" for cooling mode.
Air Heating Set
Temp.
• Upper Limit: 75°F~86°F (24°C~30°C) (Default: 86°F [30°C])
• Lower Limit: 61°F~71.6°F (16°C~22°C) (Default: 61°F [16°C])
Adjusts range of the "Setting Air Temperature" for
heating mode.
Water Heating Set
Temp.
• Upper Limit: 95°F~122°F (35°C~50°C) (Default: 122°F [50°C])
• Lower Limit: 68°F~93.2°F (20°C~34°C) (Default: 68°F [20°C])
Adjusts range of the "Setting Heating Flow Temperature"
for heating mode.
DHW Set Temp.
• Upper Limit: 122°F (50°C) (Default: 122°F [50°C])
• Lower Limit: 86°F~104°F (30°C~40°C) (Default: 104°F [40°C])
Adjusts range of the "Setting DHW Tank Heating Flow
Temperature" in hot water tank heating mode.
Cooling / Heating
Only Mode
Set
• Release (Default)
• Oil Recovery Options: Type 0, 1 (Default: Type 0)
Sets the operation mode lock function.
Water Supply Off
Temp.
During Cooling
Water Stop Temperature
• 61°F~77°F (16°C~25°C) (Default: 61°F [16°C])
• Fan Coil Unit Use / Not Use (Default: Use)
When operating in floor cooling, it is necessary to
stop the supply of cold water to prevent
condensation.
Functions
The tables below and on the next pages outline the functions available to the Hydro Kit.
5HJLRQDOWLWXGHPLJK\GUR.LW¶VDELOLW\WRUHDFKVWDWHGWHPSHUDWXUHV8QLWFDSDELOLW\LVUDWHGDWVHDOHYHO
Table 33: Hydro Kit User Functions.
* Deadband is the difference between the upper and lower limit setpoints.
PRE-COMMISSIONING
Functions