LESsoft configuration software
Leuze electronic
LES 36
75
TNT
35/7-2
4
V
sensor ('Transmit to Sensor'), the
Enable External Inspection Task Selection
check box must again be selected. Only then can inspection tasks be selected via the pro-
cess interface.
The upper drop-down menu
Inspection Task Selection
lets you select one of the 16
possible inspection tasks. After the selection of the inspection task, the associated param-
eters are loaded and displayed. You can edit these parameters and save the edited param-
eters under the same name.
In the
Name
field, you can assign a meaningful name (max. 12 characters) to the inspection
task selected above and save it by clicking on
Accept
.
By saving via the button
Apply Settings
,
the currently displayed
inspection task is
temporarily stored in the sensor. When switched off, the data/settings are lost.
By saving via
Configuration -> Transmit to Sensor
menu command
all inspection
tasks created
are transmitted to the sensor, where they are permanently stored.
Note!
If an inspection task was changed, permanent storage in the sensor should be performed
with
Configuration -> Transmit to Sensor
.
The common procedure for creating and storing inspection tasks is described in
Chapter 9.6, "Definition of inspection tasks" on page 93.
Operation Mode
In
Operation Mode
you can configure using
Free Running
that the LES continuously
detects and outputs measurement data (factory setting). With
Input Triggered
the LES
captures measurement data only if a rising edge is present at the trigger input or if one of
the "Ethernet Trigger" (Chapter 10.3.4) or PROFIBUS Trigger (Chapter 11.5) commands is
being used. Detailed information on this topic can be found in Chapter 4.2.3.
Activation
Under
Activation
the
Regard
setting has the effect that the laser is switched on and off
according to the level at the activation input or via PROFIBUS. Detailed information on this
topic can be found in Chapter 4.2.2.
When the
Disregard
setting has been selected, the laser always remains switched on,
independent from the level at the activation input or the PROFIBUS activation (factory
setting).
Trigger Output Mode
Under
Trigger Output Mode
you can activate the cascading output using
Cascading
.
Detailed information on this topic can be found in Chapter 4.2.4. When the
Disable
setting
has been selected, the cascading output will not be set (factory setting).
Light Exposure
Using
Light Exposure
you can control the exposure duration of the laser during measure-
ment value detection and adapt it to the reflective properties of the objects to be detected.
Select an exposure setting that displays a continuous line around the object contour.
Then try to achieve a line on a flat surface that is as continuous as possible.